Outdoor units (combination) – Toshiba SUPER MODULAR MULTI HFC R-410A User Manual
Page 60
60
Outdoor units (combination)
Rating
hp
22
22
Cooling only system MMY
AP2201T8
AP2211T8
Heat pump system MMY
AP2201HT8
AP2211HT8
Outdoor unit type
Inverter
Inverter
Inverter
Inverter
Inverter
Outdoor unit combination
cooling only MMY-MAP
0801T8
0801T8
0601T8
1201T8
1001T8
Outdoor unit combination
heat pump MMY-MAP
0801HT8
0801HT8
0601HT8
1201HT8
1001HT8
Cooling capacity
kW
61.5
61.5
Heating capacity
kW
69.0
69.0
Power supply
V-ph-Hz
400-3-50 ± 10%
400-3-50 ± 10%
400-3-50 ± 10%
400-3-50 ± 10%
400-3-50 ± 10%
Voltage range
V
380-415
380-415
380-415
380-415
380-415
Power input, cooling
kW
17.39
20.41
Power factor, cooling
%
95
95
Operating current, cooling
A
26.42
31.01
EER, cooling
kW/kW
3.54
3.01
Starting current
A
1.0
1.0
Power input, heating
kW
17.35
18.68
Power factor, heating
%
95
95
Operating current, heating
A
26.36
28.38
COP, heating
kW/kW
3.98
3.69
Starting current
A
1.0
1.0
Unit appearance
Silky shade (Munsell 1Y8.5/0.5)
Dimensions
Height
mm
1800
1800
1800
1800
1800
Width
mm
990
990
990
990
990
Depth
mm
750
750
750
750
750
Total weight - cooling only unit
kg
256
256
227
256
256
Total weight - heat pump unit
kg
258
258
228
258
258
Heat exchanger
Finned type
Sound power level
dB(A)
74.5
74.5
Sound pressure level
dB(A) at 1 m 61.5
61.5
Fan type
Propeller
Propeller
Propeller
Propeller
Propeller
Motor power input
kW
0.6
0.6
0.6
0.6
0.6
Air flow
l/s
2750
2750
2500
2917
2917
m
3
/h
9900
9900
9000
10500
10500
Compressor type
Hermetic
Hermetic
Hermetic
Hermetic
Hermetic
Motor power input
kW
2.3 x 2
2.3 x 2
1.4 x 2
4.2 x 2
3.1 x 2
Refrigerant charge R-410A*
Cooling
kg
11.0
11.0
8.0
11.0
11.0
Heating
kg
12.5
12.5
8.5
12.5
12.5
Pipework**
Suction line type - diameter
in
Brazed - 7/8
Brazed - 7/8
Brazed - 3/4
Brazed - 1-1/8
Brazed - 7/8
Liquid line type - diameter
in
Flare - 1/2
Flare - 1/2
Flare - 3/8
Flare - 1/2
Flare - 1/2
Balance pipe type - diameter
in
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Maximum equivalent length separation
m
175
175
175
175
175
Maximum actual piping length
m
150 (if equivalent bend length is longer, equivalent length is standard)
Maximum total piping length
m
300
300
300
300
300
Maximum lift - indoor unit above/below***
m
40/50
40/50
40/50
40/50
40/50
Control wiring
Shielded wire 1.25 mm
2
x 2 cores up to 2000 m
Central remote controller
Shielded wire 1.25 mm
2
x 2 pieces up to 1000 m, 2.0 mm
2
x 2 pieces up to 2000 m
Max. number of connectable indoor units
37
37
High-pressure switch
MPa
Off: 2.90/On: 3.73
Protection devices
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,
overcurrent relay
Operating range, cooling†
°C
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db
Operating range, heating†
°C
-20 to 16 wb
-20 to 16 wb
-20 to 16 wb
-20 to 16 wb
-20 to 16 wb
Rated conditions:
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.
*
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.
**
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.
***
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.
†
Please refer to page 24.