Indoor units high-wall units (1 series) – Toshiba SUPER MODULAR MULTI HFC R-410A User Manual
Page 53
53
Indoor units
High-wall units (1 Series)
Model MMK-AP
0071H
0091H
0121H
0151H
0181H
0241H
Cooling capacity*
kW
2.2
2.8
3.6
4.5
5.6
7.1
Heating capacity
kW
2.5
3.2
4.0
5.0
6.3
8.0
Electrical data
Power supply
V-ph-Hz
230-1-50 (voltage range 220-240 V) - power supply to indoor unit only
Operating current
A
0.30
0.30
0.30
0.32
0.32
0.35
Power input
kW
0.035
0.035
0.035
0.037
0.037
0.040
Starting current
A
0.36
0.36
0.36
0.42
0.42
0.47
Unit appearance
Suction grille and side panel
Silky mist (Munsell 1Y 8.9/0.5)
Discharge grille
City grey (Munsell N6.5)
Bottom surface
Silky mist (Munsell 1Y 8.9/0.5)
Unit dimensions
Height
mm
368
368
368
368
368
368
Width
mm
895
895
895
1055
1055
1430
Depth
mm
210
210
210
210
210
210
Unit weight
kg
18
18
18
19
19
25
Heat exchanger
Finned tube
Sound proofing/heat insulating material
Non-flammable insulation
Fan type
Tangential fan
Fan motor power input
W
30
30
30
30
30
30
Air flow
High
l/s
167
167
167
217
217
333
Medium
l/s
150
150
150
183
183
283
Low
l/s
133
133
133
167
167
250
Air flow
High
m
3
/h
600
600
600
780
780
1200
Medium
m
3
/h
540
540
540
660
660
1020
Low
m
3
/h
480
480
480
600
600
900
Sound power level (high/medium/low)
dB(A)
52/47/44
52/47/44
52/47/44
55/51/48
55/51/48
55/51/48
Sound pressure level (high/medium/low)** dB(A)
39/34/31
39/34/31
39/34/31
42/38/35
42/38/35
42/38/35
Air filter
Standard single filter supplied
Controller
Remote controller
Connection pipes
Gas connection diameter
in
3/8
3/8
3/8
1/2
1/2
5/8
Liquid connection diameter
in
1/4
1/4
1/4
1/4
1/4
3/8
Drain connection, nom. dia (polyvinyl tube)
in
3/4
3/4
3/4
3/4
3/4
3/4
Rated conditions:
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
**
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.