Indoor units ceiling-suspended units – Toshiba SUPER MODULAR MULTI HFC R-410A User Manual
Page 52

52
Indoor units
Ceiling-suspended units
Model MMC-AP
0151H
0181H
0241H
0271H
0361H
0481H
Cooling capacity*
kW
4.5
5.6
7.1
8.0
11.2
14.0
Heating capacity
kW
5.0
6.3
8.0
9.0
12.5
16.0
Electrical data
Power supply
V-ph-Hz
230-1-50 (voltage range 220-240 V) - power supply to indoor unit only
Operating current
A
0.29
0.32
0.42
0.42
0.78
0.84
Power input
kW
0.033
0.038
0.050
0.050
0.091
0.110
Starting current
A
0.43
0.48
0.62
0.62
1.17
1.25
Unit appearance
White (Munsell 10Y 9.3/0.4)
Unit dimensions
Height
mm
210
210
210
210
210
210
Width
mm
910
910
1180
1180
1595
1595
Depth
mm
680
680
680
680
680
680
Unit weight
kg
22
22
26
26
34
34
Heat exchanger
Finned tube
Sound proofing/heat insulating material
Non-flammable insulation
Fan type
Centrifugal fan
Fan motor power input
W
30
30
40
40
80
80
Air flow
High
l/s
200
217
308
308
458
500
Medium
l/s
167
183
250
250
383
433
Low
l/s
150
150
233
233
333
367
Air flow
High
m
3
/h
720
780
1110
1110
1650
1800
Medium
m
3
/h
600
660
900
900
1380
1560
Low
m
3
/h
540
540
840
840
1200
1320
Sound power level (high/medium/low)
dB(A)
48/45/43
49/46/43
51/49/46
51/49/46
54/51/48
56/53/50
Sound pressure level (high/medium/low)** dB(A)
35/32/30
36/33/30
38/36/33
38/36/33
41/38/35
43/40/37
Air filter
Standard long-life filter supplied
Controller
Remote controller
Room thermostat
Supplied
Connection pipes
Gas connection diameter
in
1/2
1/2
5/8
5/8
5/8
5/8
Liquid connection diameter
in
1/4
1/4
3/8
3/8
3/8
3/8
Drain connection, nom. dia (polyvinyl tube)
in
3/4
3/4
3/4
3/4
3/4
3/4
Rated conditions:
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
**
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.