Indoor units slim duct units – Toshiba SUPER MODULAR MULTI HFC R-410A User Manual
Page 51

51
Indoor units
Slim duct units
Model MMD-AP
0071SPH
0091SPH
0121SPH
0151SPH
0181SPH
Cooling capacity*
kW
2.2
2.8
3.6
4.5
5.6
Heating capacity
kW
2.5
3.2
4.0
5.0
6.3
Electrical data
Power supply
V-ph-Hz
230-1-50 (voltage range 220-240 V) - power supply to indoor unit only
Operating current
A
0.29
0.29
0.31
0.32
0.39
Power input
kW
0.039
0.039
0.043
0.045
0.054
Starting current
A
0.51
0.51
0.54
0.56
0.68
Unit appearance
Zinc hot dipping steel plate
Unit dimensions
Height
mm
210
210
210
210
210
Width
mm
845
845
845
845
845
Depth
mm
645
645
645
645
645
Unit weight
kg
22
22
22
23
23
Heat exchanger
Finned tube
Sound proofing/heat insulating material
Polyethylene foam and polyurethane foam
Fan type
Centrifugal fan
Fan motor power input
W
60
60
60
60
60
Air flow
High
l/s
150
150
167
192
217
Medium
l/s
131
131
145
167
189
Low
l/s
111
111
125
145
161
Air flow
High
m
3
/h
540
540
600
690
780
Medium
m
3
/h
470
470
520
600
680
Low
m
3
/h
400
400
450
520
580
Static pressure (factory setting)
Pa
6
6
5
5
4
Static pressure (max.)
Pa
-16/-31/-46
-16/-31/-46
-15/-30/-45
-15/-30/-45
-14/-29/-44
Air filter pressure loss
Pa
4
4
5
5
6
Lower air inlet
Sound power level (high/medium/low)
dB(A)
49/46/43
49/46/43
51/48/45
52/49/46
53/51/49
Sound pressure level (high/medium/low)**
dB(A)
36/33/30
36/33/30
38/35/32
39/36/33
40/38/36
Rear air inlet
Sound power level (high/medium/low)
dB(A)
41/39/37
41/39/37
42/40/38
45/43/41
46/44/42
Sound pressure level (high/medium/low)**
dB(A)
28/26/24
28/26/24
29/27/25
32/30/28
33/31/29
Air filter
Standard long-life filter supplied
Controller
Remote controller
Connection pipes
Gas connection diameter
in
3/8
3/8
3/8
1/2
1/2
Liquid connection diameter
in
1/4
1/4
1/4
1/4
1/4
Drain connection, nom. dia (polyvinyl tube)
in
1
1
1
1
1
Rated conditions:
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
**
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.