Indoor units
Floor-mounted cabinet units
Model MMF-AP
0151H
0181H
0241H
0271H
0361H
0481H
0561H
Cooling capacity*
kW
4.5
5.6
7.1
8.0
11.2
14.0
16.0
Heating capacity
kW
5.0
6.3
8.0
9.0
12.5
16.0
18.0
Electrical data
Power supply
V-ph-Hz
230-1-50 (voltage range 220-240 V) - power supply to indoor unit only
Operating current
A
0.67
0.67
0.88
0.88
1.29
1.60
1.60
Power input
kW
0.150
0.150
0.190
0.190
0.280
0.350
0.350
Power factor
%
97
97
94
94
94
95
95
Starting current
A
0.90
0.90
1.10
1.10
1.70
2.10
2.10
Unit appearance
W: Silky shade (1Y 8.5/0.5)
Unit dimensions
Height
mm
1750
1750
1750
1750
1750
1750
1750
Width
mm
600
600
600
600
600
600
600
Depth
mm
210
210
210
210
390
390
390
Unit weight
kg
48
48
49
49
65
65
65
Heat exchanger
Finned tube
Sound proofing/heat insulating material
Non-flammable insulation
Fan type
Centrifugal fan
Fan motor power input
W
37
37
63
63
110
160
160
Air flow
High
l/s
250
250
333
333
533
600
600
Medium
l/s
217
217
283
283
467
517
517
Low
l/s
183
183
233
233
383
433
433
Air flow
High
m
3
/h
900
900
1200
1200
1920
2160
2160
Medium
m
3
/h
780
780
1020
1020
1680
1860
1860
Low
m
3
/h
660
660
840
840
1380
1560
1560
Sound power level (high/medium/low)
dB(A)
59/56/51
59/56/51
62/58/53
62/58/53
64/61/57
67/63/59
67/63/59
Sound pressure level (high/medium/low)** dB(A)
46/43/38
46/43/38
49/45/40
49/45/40
51/48/44
54/50/46
54/50/46
Air filter
Standard single filter supplied
Controller
Remote controller
Connection pipes
Gas connection diameter
in
1/2
1/2
5/8
5/8
5/8
5/8
5/8
Liquid connection diameter
in
1/4
1/4
3/8
3/8
3/8
3/8
3/8
Drain connection, nom. dia***
in
3/4
3/4
3/4
3/4
3/4
3/4
3/4
Rated conditions:
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
**
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.
***
Male screw connection one side