6. Control wiring diagram
1. All control wiring is 2-core non-polarity wire.
2. Be sure to use shielded wire for the following wiring to prevent noise disturbance.
•
Outdoor-outdoor/indoor-indoor/outdoor-indoor control wiring, central control wiring.
Table 1
Control wiring between indoor and outdoor units (L1, L2, L3)
Central control wiring (L4)
Wiring
2-core, non-polarity
Type
Shielded wire
Size
1.25 mm²: Up to 1000 m
Length
2.0 mm²: Up to 2000 m (*1)
(*1): Total of control wiring length for all refrigerant circuits ( L1 + L2 + L3 + L4 )
Table 2
Control wiring between outdoor units (L5)
Wiring
2-core, non-polarity
Type
Shielded wire
Size
1.25 mm² to 2.0 mm²
Length
Up to 100 m (L5)
Table 3
Remote controller wiring (L6, L7)
Wire
2-core
Size
0.5 mm² to 2.0 mm²
Length
•
Up to 500 m ( L6 + L7 ).
•
Up 400 m in case of wireless remote controller in group control.
•
Up to 200 m total length of control wiring between indoor units ( L6 ).
Central control
device
Super Modular Multi System