Indoor units standard ducted units – Toshiba SUPER MODULAR MULTI HFC R-410A User Manual
Page 49
49
Indoor units
Standard ducted units
Model MMD-AP
0071BH 0091BH 0121BH 0151BH 0181BH 0241BH 0271BH 0301BH 0361BH 0481BH 0561BH
Cooling capacity*
kW
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
11.2
14.0
16.0
Heating capacity
kW
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
18.0
Electrical data
Power supply
V-ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only
Operating current
A
0.29
0.29
0.34
0.34
0.43
0.52
0.52
0.61
0.83
0.98
0.98
Power input
kW
0.033
0.033
0.039
0.039
0.050
0.060
0.060
0.071
0.107
0.128
0.128
Starting current
A
0.50
0.50
0.59
0.59
0.75
0.90
0.90
1.05
1.44
1.70
1.70
Unit appearance
Zinc hot dipping steel plate
Unit dimensions
Height
mm
320
320
320
320
320
320
320
320
320
320
320
Width
mm
550
550
550
700
700
1000
1000
1000
1350
1350
1350
Depth
mm
800
800
800
800
800
800
800
800
800
800
800
Unit weight
kg
28
28
28
32
32
43
43
43
55
55
55
Heat exchanger
Finned tube
Sound proofing/heat insulating material
Non-flammable insulation
Fan type
Centrifugal fan
Fan motor power input
W
120
120
120
120
120
120
120
120
120
120
120
Air flow
High
l/s
133
133
158
181
217
317
317
350
450
550
550
Medium
l/s
117
117
136
150
183
275
275
300
392
475
475
Low
l/s
95
95
111
133
150
242
242
242
333
414
414
Air flow
High
m
3
/h
480
480
570
650
780
1140
1140
1260
1620
1980
1980
Medium
m
3
/h
420
420
490
540
660
990
990
1080
1410
1710
1710
Low
m
3
/h
340
340
400
480
540
870
870
870
1200
1490
1490
Static pressure (factory setting)
Pa
40
40
40
40
40
40
40
40
40
40
40
Static pressure (max.)
Pa
100
100
100
100
100
100
100
100
100
100
100
Sound power level (high/medium/low)
dB(A)
43/41/39 43/41/39 44/42/40 44/42/40 45/43/41 46/44/42 46/44/42 47/45/42 49/47/45 51/49/45 51/49/45
Sound pressure level (high/medium/low)** dB(A)
30/28/26 30/28/26 31/29/27 31/29/27 32/30/28 33/31/29 33/31/29 34/32/29 36/34/32 38/36/32 38/36/32
Air filter
Standard long-life filter supplied
Controller
Remote controller
Connection pipes
Gas connection diameter
in
3/8
3/8
3/8
1/2
1/2
5/8
5/8
5/8
5/8
5/8
5/8
Liquid connection diameter
in
1/4
1/4
1/4
1/4
1/4
3/8
3/8
3/8
3/8
3/8
3/8
Drain connection, nom. dia (polyvinyl tube)
in
1
1
1
1
1
1
1
1
1
1
1
Panel dimensions
Height
mm
9
9
9
9
9
9
9
9
9
9
9
Width
mm
630
630
630
780
780
1080
1080
1080
1430
1430
1430
Depth
mm
500
500
500
500
500
500
500
500
500
500
500
Panel weight
kg
3.5
3.5
3.5
4.0
4.0
6.0
6.0
6.0
7.0
7.0
7.0
Rated conditions:
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
**
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.