Indoor units
2-way ceiling cassettes
Model MMU-AP
0071WH
0091WH
0121WH
0151WH
0181WH
0241WH
0271WH
0301WH
Cooling capacity*
kW
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
Heating capacity
kW
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
Electrical data
Power supply
V-ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only
Operating current
A
0.31
0.31
0.31
0.32
0.32
0.46
0.46
0.47
Power input
kW
0.070
0.070
0.070
0.072
0.072
0.105
0.105
0.106
Power factor
%
97
97
97
97
97
99
99
98
Starting current
A
0.47
0.47
0.47
0.60
0.60
0.89
0.89
0.98
Unit appearance
Zinc hot dipping steel plate - heat insulating material attached
Unit dimensions
Height
mm
398
398
398
398
398
398
398
398
Width
mm
830
830
830
1350
1350
1350
1350
1350
Depth
mm
550
550
550
550
550
550
550
550
Unit weight
kg
33
33
33
44
44
48
48
48
Heat exchanger
Finned tube
Sound proofing/heat insulating material
Non-flammable insulation
Fan type
Centrifugal fan
Fan motor power input
W
53
53
53
39
39
53
53
53
Air flow
High
l/s
158
158
158
217
217
317
317
350
Medium
l/s
142
142
142
195
195
267
267
317
Low
l/s
125
125
125
167
167
200
200
267
Air flow
High
m
3
/h
570
570
570
780
780
1140
1140
1260
Medium
m
3
/h
510
510
510
700
700
960
960
1140
Low
m
3
/h
450
450
450
600
600
720
720
960
Sound power level (high/medium/low)
dB(A)
47/45/43
47/45/43
47/45/43
48/46/43
48/46/43
51/48/46
51/48/46
53/50/47
Sound pressure level (high/medium/low)** dB(A)
34/32/30
34/32/30
34/32/30
35/33/30
35/33/30
38/35/33
38/35/33
40/37/34
Air filter
Standard long-life filter supplied
Controller
Remote controller
Connection pipes
Gas connection diameter
in
3/8
3/8
3/8
1/2
1/2
5/8
5/8
5/8
Liquid connection diameter
in
1/4
1/4
1/4
1/4
1/4
3/8
3/8
3/8
Drain connection, nom. dia (polyvinyl tube)
in
1
1
1
1
1
1
1
1
Ceiling panel model number
RBC-UW136PG
RBC-UW266PG
Panel colour
Light ivory (Munsell 10Y 9/0.5)
Panel dimensions
Height
mm
8
8
8
8
8
8
8
8
Width
mm
1000
1000
1000
1520
1520
1520
1520
1520
Depth
mm
650
650
650
650
650
650
650
650
Panel weight
kg
8
8
8
11
11
11
11
11
Rated conditions:
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
**
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.