Electrical data, Electric power – Trane PKGP-PRC001-EN User Manual
Page 27

PKGP-PRC001-EN
27
Table ED-2 — Electrical Characteristics — Power Exhaust Accessory
Accessory
Operating
Amps
Tons
Voltage
Phase
HP
RPM
FLA
LRA
208-230
1
3/4
1040
6.6
13.5
460
1
3/4
1040
3.2
8.4
575
1
3/4
1040
2.1
5.2
Table ED-1 — Unit Wiring
Standard Indoor Fan Motor
Oversize Indoor Fan Motor
Unit
Minimum
Maximum Fuse Size
Minimum
Maximum Fuse Size
Unit
Operating
Circuit
or Maximum
Circuit
or Maximum
Tons
Model No.
Voltage Range
Ampacity
Circuit Breaker
1
Ampacity
Circuit Breaker
1
WC*150B3
187-253
66.0
80
72.0
80
12½
WC
*
150B4
414-506
31.0
40
34.0
40
WC
*
150BW
517-633
25.0
30
28.0
35
WC
*
180B3
187-253
76.0
90
82.0
100
15
WC
*
180B4
414-506
39.0
45
42.0
50
WC
*
180BW
517-633
31.0
35
33.0
40
WC
*
240B3
187-253
96.0
125
103.0
125
20
WC
*
240B4
414-506
49.0
60
53.0
60
WC
*
240BW
517-633
38.0
45
41.0
50
Note:
1. HACR type circuit breaker per NEC.
Electrical
Data
*
Indicates both downflow and horizontal units.
12½, 15, 20