beautypg.com

15, 20 ton) general data – Trane PKGP-PRC001-EN User Manual

Page 13

background image

PKGP-PRC001-EN

13

(15, 20 Ton)

General
Data

*Indicates both downflow and horizontal units.

Table GD-2 — General Data

15 Ton Downflow and Horizontal Units

20 Ton Downflow and Horizontal Units

WC*180B3, B4, BW

WCD240B3, B4, BW

WCH240B3, B4, BW

Cooling Performance

1

Gross Cooling Capacity

180,000

233,000

237,000

EER

2

9.6

9.8

10.5

Nominal CFM / ARI Rated CFM

6,000 / 5,300

8,000 / 8,000

8,000/7,000

ARI Net Cooling Capacity

168,000

222,000

224,000

Integrated Part Load Value

3

10.0

9.7

10.3

System Power KW

17.50

22.2

21.3

Heating Performance

1

High Temp. Btuh Rating

166,000

208,000

204,000

System Power KW/COP

15.69/3.10

19.65/3.10

19.29/3.10

Low Temp. Btuh Rating

88,000

118,000

118,000

System Power KW/COP

13.12/2.1

18.75/2.0

17.29/2.00

Compressor
No./Type

2/Scroll

2/Scroll

2/Scroll

Sound Rating (BELS)

4

9.2

9.4

9.4

Outdoor Coil — Type

Hi-Performance

Hi-Performance

Hi-Performance

Tube Size (in.) OD

.375

.375

.375

Face Area (sq ft)

27.12

35.3

35.3

Rows/FPI

3/16

3/16

3/16

Refrigerant Control

Expansion Valve

Expansion Valve

Expansion Valve

Indoor Coil — Type

Hi-Performance

Hi-Performance

Hi-Performance

Tube Size (in.)

.375

.375

.375

Face Area (sq ft)

17.50

26.00

26.00

Rows/FPI

3/15

3/15

3/15

Refrigerant Control

Short Orifice

Capillary Tube

Capillary Tube

Drain Connection No./Size (in.)

1/1.00 NPT

1/1.00 NPT

1/1.00 NPT

Outdoor Fan — Type

Propeller

Propeller

Propeller

No. Used/Diameter (in.)

2/26

2/28

2/28

Drive Type/No. Speeds

Direct/1

Direct/1

Direct/1

CFM

10,200

13,800

13,800

No. Motors/HP

2/.50

2/1.0

2/1.0

Motor RPM

1,100

1,125

1,125

Indoor Fan — Type

FC Centrifugal

FC Centrifugal

FC Centrifugal

No. Used

1

1

1

Diameter x Width (in.)

15 x 15

18 x 18

18 x 18

Drive Type/No. Speeds

Belt/1

Belt/1

Belt/1

No. Motors

1

1

1

Motor HP (Standard/Oversized)

3.0/5.0

5.0/7.5

5.0/7.5

Motor RPM (Standard/Oversized)

1,740/3,450

3,450/3,450

3,450/3,450

Motor Frame Size (Standard/Oversized)

145T/145T

184T/184T

184T/184T

Filters — Type Furnished

6

Throwaway

Throwaway

Throwaway

(No.) Size Recommended (in.)

(2) 20 x 20 x 2

(4) 20 x 20 x 2

(8) 20 x 25 x 2

(4) 20 x 25 x 2

(4) 20 x 25 x 2

Refrigerant Charge (Lbs of R-22)

5

19.9/9.9 Circuit

22.0/21.0 Circuit

22.0/21.0 Circut

Notes:
1. Cooling Performance and Heating Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat.

ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.

2. EER is rated at ARI conditions and in accordance with ASHRAE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 340. Units are rated at 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Optional 2 inch pleated filter also available.