Table 4-6 (continued) – Trane INTELLIPAK ™ ™ ™ ™ ™ Commercial Single-Zone Rooftop Air Conditioners with CV or VAV Control User Manual
Page 89
![background image](/manuals/215218/89/background.png)
87
Table 4-6 (Continued)
50 Ton Operating Pressure Curve (All Compressors and Condenser Fans, per ckt; "On")
COOLING CYCLE PRESSURE CURVE
(Based on Indoor Airflow of 400 CFM / Ton)
FULL LOAD
180
200
220
240
260
280
300
320
340
360
380
50
55
60
65
70
75
80
85
90
95
100
SUCTION PRESSURE, PSIG
DISCHARG
E PRESSURE, PSIG
105 F OD Ambient
95 F OD Ambient
85 F OD Ambient
75 F OD Ambient
65 F OD Ambient
To Check Operating Pressures
1. Start the unit and allow the pressures to stabilize.
2. Measure the outdoor air dry bulb temperature (F)
entering the condenser coil.
3. Measure the discharge and suction pressure (psig)
next to the compressor.
4. Plot the outdoor dry bulb temperature and the
operating suction pressure (psig) onto the chart.
5. At the point of intersection, read to the left for the
discharge pressure. The measured discharge
pressure should be within ± 7 psig of the graph.
55 Ton Operating Pressure Curve (All Compressors and Condenser Fans, per ckt, "On")
50
55
60
65
70
75
80
85
90
95
100
180
200
220
240
260
280
300
320
340
360
55 Ton Operating Pressure Curve (All Compressors and Condenser Fans, per ckt, "On")
Full Load
(Based on Indoor Airfow of 400 CFM / Ton)
Cooling Cycle Pressure Curve
65 F OD Ambient
75 F OD Ambient
85 F OD Ambient
95 F OD Ambient
105 F OD Ambient
D
is
c
har
ge
P
res
s
u
re
, P
S
IG
Suction Pressure, PSIG