Trane INTELLIPAK ™ ™ ™ ™ ™ Commercial Single-Zone Rooftop Air Conditioners with CV or VAV Control User Manual
Page 43

42
Table 3-7 (Continued)
Electrical Service Sizing Data (20 through 130 Ton)
Unit
200/60/3, Nominal
230/60/3, Nominal
460/60/3, Nominal 575/60/3, Nominal
Component(s)
(180-220V Utiliz.)
(207-253V Utiliz.)
(414-506V Utiliz.)
(517-633V Utiliz.)
Electric Heat
FLA (3)
FLA (3)
FLA (3)
FLA (3)
(SEHF Only):
30 Kw
83.3
72.2
36.1
28.9
50 Kw
138.8
120.3
60.1
48.1
70 Kw
194.3
168.4
84.2
67.4
90 Kw
249.8
216.5
108.3
86.6
110 Kw
305.3
264.6
132.3
105.9
130 Kw
-n/a-
-n/a-
156.4
125.1
150 Kw
-n/a-
-n/a-
180.4
144.3
170 Kw
-n/a-
-n/a-
204.5
163.6
190 Kw
-n/a-
-n/a-
228.5
182.8
Combustion
FLA
FLA
FLA
FLA
Blower Motor
(SFHF Only):
235, 350, 500 MB
2.1
1.8
0.9
0.7
850 & 1,000 MBh
2.8
2.4
1.2
1
Unit Tonnage
No. of Compressors Tonnage
Type
Designation
20 Ton Std and Hi-Capacity
Two
9 - Ton
Scrolls
A & B
25 Ton Std and Hi-Capacity
One
14 - Ton
Scroll
B
One
9 - Ton
Scroll
A
30 Ton Std and Hi-Capacity
Two
14 - Ton
Scrolls
A & B
40 Ton Std and Hi-Capacity
Four
9 - Ton
Scrolls
1A, 1B, 2A, 2B
50 Ton Std and Hi-Capacity
Two
14 - Ton
Scrolls
1B & 2B
Two
9 - Ton
Scrolls
1A & 2A
55 Ton Std and Hi-Capacity
Four
14 - Ton
Scrolls
1A, 1B, 2A, 2B
60Ton Std and Hi-Capacity
Four
14 - Ton
Scrolls
1A, 1B, 2A, 2B
70 / 75 Ton Std
Four
9 - Ton
Scrolls
1A, 1B, 2A, 2B
Two
14 - Ton
Scrolls
1 C & 2C
75 Ton Hi-Capacity
Four
10 - Ton
Scrolls
1A & 2A, 1B & 2B
Two
15- Ton
Scrolls
1C, 2C
90 Ton
Two
10 - Ton
Scrolls
1A & 2A
Four
15 - Ton
Scrolls
1 ,2B & 1,2C
105 Ton
Six
15 - Ton
Scrolls
1,2A, 1,2B, 1,2C
115 Ton
Four
15 - Ton
Scrolls
1,2A & 1,2B
Four
10 - Ton
Scrolls
1,2C & 1,2D
130 Ton
Eight
14 - Ton
Scrolls
1,2A, 1,2B, 1,2C, 1,2D
Note:
3. "Full load amp" values shown for the electric heat were determined at 480 and 600 volts, respectively.