Appendix 2 response time – Toshiba Tosvert RS485 User Manual
Page 69
![background image](/manuals/210864/69/background.png)
E6581315
68
Appendix 2 Response time
The communication response time can be calculated from data communication time and inverter
processing time.
When wishing to know the communication response time, calculate using the
following as a reference
Data transmission time
bits
of
number
d
transmitte
bytes
of
number
rate
baud
1
time
on
transmissi
Data
Ч
Ч
=
* Number of bits = start bit + data frame length + parity bit + stop bit
* Minimum number of bits = 1 + 8 + 0 + 1 = 10 bits
* Maximum number of bits = 1 + 8 + 1 + 2 = 12 bits
4.6ms
11
8
19200
1
time
on
transmissi
Data
=
Ч
Ч
=
Data processing time of inverter
Data processing time: maximum 8 ms
Inverter
→ PC
Data transmission time
Response time
PC
→ Inverter
Data transmission time
Interval corresponding to 3.5 bytes
Data processing time of inverter (Approx. 8 ms)