Toshiba Tosvert RS485 User Manual

Page 55

background image

E6581315

54

„

Inverter operating command mode status (FD45, FE45)

The monitor of the command mode that the present condition is enabled

Command mode status (current status): “Communication Number FD45”
Command mode status (status immediately before the occurrence of a trip): “Communication Num-
ber

Data

Enabled command

0

Terminal input enabled

1

Operation panel input enabled

2

Operation panel RS485 (2-wire) communication input

3

Internal RS485 (4-wire) communication input

4

Communication option input

„

Inverter operating frequency mode status (FD46, FE46)

The monitor of the frequency command mode that the present condition is enabled
Note that Preset speed operation frequencies is given the priority independent of the frequency
mode, in which case this monitor will be disabled, in case Preset speed operation frequencies is
selected.

Frequncy mode status (current status): Communication Number FD46
Frequncy mode status (status immediately before the occurrence of a trip): Communication

Number FE46

Data

Enabled frequency

1

VI/II input

2

RR/S4 input

3

RX input

4

Operation panel input enabled

5

Operation panel RS485 (2-wire) communication input

6

Internal RS485 (4-wire) communication input

7

Communication option input

8

Optional AI1

9

Optional AI2

10

UP/DOWN frequency

11

RP pulse input

12

High-speed pulse input

13

Binary/BCD input

255

Preset speed operation