63

„

Command

parameters

For those parameters that contain data only in the RAM and not in the EEPROM, their data return to
initial values when the power is turned off, in failure resetting, or when standard shipment settings
are set. Note that parameters without data storage in the EEPROMs will be written in the RAM only
even if the command W (writing in EEPROMs and RAM) is executed.

Q 

Commands                          NOTE : Data is expressed in decimal notation.

Communica-

tion

Num-

ber.(HEX)

Function

Adjustment Range

Min.

Setting

Unit

Initial

Value

Write

During

Operation

EEP

ROM

FA00

Command 1 (2-wire RS485)

1

0 to 65535

0

yes

None

FA01

Frequency command value (2-
wire RS485)

1

0 to Max. frequency
()

0.01Hz

0

yes

None

FA03

Operation panel operation
frequency *

2

Low-limit frequency
() to High-limit
frequency ()

0.01Hz

0

yes

Available

FA04

Command 1 (4-wire RS485)

1

0 to 65535

0

yes

None

FA05

Frequency command value (4-
wire RS485)

1

0 to Max. frequency
()

0.01Hz

0

yes

None

FA10

Panel key selection

4

0: Main unit
1: Comunication

0

yes

None

FA11

External communication key
data

4

0 to 65535

0

yes

None

FA20

Command 2 (2-wire RS485)

1

0 to 65535

0

yes

None

FA22

Command 2 (4-wire RS485)

1

0 to 65535

0

yes

None

FA30

Torque command value (2-wire
RS485)

-250.00 to 250.00

0.01%

0

yes

None

FA32

Torque command value (4-wire
RS485)

-250.00 to 250.00

0.01%

0

yes

None

FA50

Terminal output data

3

0 to 255

1

0

yes

None

FA51

FM analog output data

3

0 to 2047
(11-bit resolution)

1

0

yes

None

FA52

AM analog output data

3

0 to 2047
(11-bit resolution)

1

0

yes

None

FA53

MON1 analog output data

3

0 to 2047
(11-bit resolution)

1

0

yes

None

FA54

MON2 analog output data

3

0 to 2047
(11-bit resolution)

1

0

yes

None

FA65

Select display by communica-
tion

4

0 to 2

1

yes

Available

FA66

Numerical display data

4

0-9999

1

0

yes

Available

FA67

Decimal point position

4

0 to 2

0

yes

Available

FA68

LED data for unit 0

4

0 to 3

0

yes

Available

FA70

ASCII display data 1
First digit from left

4

0 to 127

100
(‘d’)

yes

Available

FA71

ASCII display data 1
Second digit from left

4

0 to 255

65

(‘A’)

yes

Available

FA72

ASCII display data 1
Third digit from left

4

0 to 255

116

(‘t’)

yes

Available

FA73

ASCII display data 1
Fourth digit from left

4

0 to 127

65

(‘A’)

yes

Available

FA74

LED data for unit1

4

0 to 3

0

yes

Available

FA75

ASCII display data 2
First digit from left

4

0 to 127

48

(‘0’)

yes

Available

FA76

ASCII display data 2
Second digit from left

4

0 to 255

48

(‘0’)

yes

Available

FA77

ASCII display data 2
Third digit from left

4

0 to 255

48

(‘0’)

yes

Available

FA78

ASCII display data 2
Fourth digit from left

4

0 to 127

48

(‘0’)

yes

Available

FA79

LED data for unit 2

4

0 to 3

0

yes

Available

FA80

Block communication mode

4

0 to 1

0

yes

Available

This manual is related to the following products: