Loop-control CPU Units

Loop Controller Element Specifications

Loop Controller Element Specifications

Item

Specifications

Model

CJ1G-CPU42P

CJ1G-CPU43/44/45P(-GTC)

Operation method

Function block method

Loop Controller element

LCB01

LCB03

Function
block analog
operations

Control and
operation
blocks

PID and other control
functions, square root op-
eration, time operations,
pulse train operation, and
other operation functions
for various processes.

50 blocks max.

300 blocks max.

Sequence
control

Step ladder
program
blocks

Logic sequence and step
sequence functions

20 blocks max.
2,000 commands total
100 commands max. per block
Separable into 100 steps max.

200 blocks max.
4,000 commands total
100 commands max. per block
Separable into 100 steps max.

I/O blocks

Field terminal
blocks

Analog I/O function with
Analog I/O Unit, contact
I/O function with Basic I/O
Unit

30 blocks max.

CJ1G-CPU43P: 30 blocks max.
CJ1G-CPU44/45P: 40 blocks max.

User link
tables

Analog data I/O and con-
tact data I/O function for
CPU Unit

2,400 data items max.

HMI function

I/O function for the speci-
fied bank of the EM Area
in the CPU Unit for func-
tion block ITEM data used
for Control, Operation,
External Controller, and
System Common blocks
for the HMI function.

Allocated 1 EM Area bank
Operation and Control blocks:
50 blocks max.

× 20 send/receive words

System Common blocks:
20 send/receive words

Allocated 1 EM Area bank
Operation and Control blocks:
300 blocks max.

× 20 send/receive words

System Common blocks:
20 send/receive words

System
Common
block

System common opera-
tion cycle setting, run/
stop command, load rate
monitor, etc.

Single block

Method for creating and transferring function blocks

Created using CX-Process Tool (purchased separately) and transferred to Loop
Controller.

External I/O response time

The time from external input of analog signals up to external output of analog signals
on a single control loop depends on the function block's operation cycle and the
CPU Unit's cycle time.

Operation cycle

0.01, 0.02, 0.05, 0.1, 0.2, 0.5, 1, or 2 s (default: 1 s) (See note.)
Can be set for each function block.
Note: 0.01, 0.02, and 0.05 s cannot be set for some blocks.

Internal operation

Number of control loops

The maximum number of loops that can be used if the LCB load rate is 80% for a

standard applications (e.g., with each loop consisting of one Ai4 Terminal, Seg-
ment Linearizer, Basic PID, and A04 terminal) is shown in the following table.

Note: Loop Controller element LCB01: 25 loops max.

Control method

PID control method

PID with 2 degrees of freedom

Control combinations

Any of the following function blocks can be combined:
Basic PID control, cascade control, feed-forward control, sample PI control, Smith
dead time compensation control, PID control with differential gap, override control,
program control, time-proportional control, etc.

Alarms

PID block internal alarms 4 PV alarms (upper upper-limit, upper limit, lower limit, lower lower-limit) and 1

deviation alarm per PID block

Alarm blocks

High/low alarm blocks, deviation alarm blocks

Operation

cycle

Maximum number

of loops

Operation

cycle

Maximum number

of loops

0.01 s

20 loops

0.2 s

150 loops
(See note.)

0.02 s

35 loops (see note)

0.5 s

0.05 s

70 loops (see note)

1 s

0.1 s

100 loops (see note) 2 s