beautypg.com

Error log error codes for the mail send function – Omron CS CJ1W-ETN21 User Manual

Page 53

background image

29

Mail Send Function Errors

Section 2-8

2-8-2

Troubleshooting Mail Send Errors with LED Indicators

Note

For more details on the error log, refer to 8-3 Error Log in the Operation Man-
ual Construction of Networks
(W420).

2-8-3

Error Log Error Codes for the Mail Send Function

When an error occurs while the Ethernet Unit is operating, the error code,
detailed error code, and time the error occurred are saved in the error log. The
following table provides a list of the error codes.

The error log can be read by sending FINS commands to the Ethernet Unit or
by using the mail receive function and specifying the ErrorLogRead com-
mand.

Details of trigger setting error

Correctly set the trigger type setting.

Specified word or specified bit data area/
address error

Correctly set the data area and address
for the specified word or bit.

Cause

Correction

RUN

ERC

ERH

LNK

HOST

Probable cause

Correction

Lit

---

Lit

---

Flashing There is an error in the server

(DNS, SMTP, or POP3) settings in
the Unit Setup.

Read the Error Status Flags and
error log and correct the setting
that caused the error. If the error
recurs, replace the CPU Unit.

Not lit

---

Flashing • An authentication error occurred

in “POP before SMTP” authenti-
cation. A communications prob-
lem occurred with the server.

• A network failure occurred in the

communications path and
caused an access timeout.

• Correctly set the POP settings

(account and password).

• Inspect the communications path

(Ethernet Unit, cable connec-
tions, hub, router, and server)
and correct any problems or
damage.

Error

code

Meaning

Detailed error code

Correction

EEPROM

1st byte

2nd byte

021A

Logic error
in setting
table

00

01: Data link
table

02: Network
parameters

03: Routing
tables

04: Setup

05: CPU Bus
Unit Words
(CIO/DM)

Recreate the data
specified by the
2nd byte of the
detailed error
code.

Saved