beautypg.com

1 overview, Overview, 1-1 overview – Omron CS CJ1W-ETN21 User Manual

Page 114

background image

90

Overview

Section 5-1

5-1

Overview

5-1-1

Overview

The Ethernet Unit can obtain the clock information from the SNTP server (see
note 1) at a particular time or when a designated bit turns ON and then
refresh the internal clock information of the CPU Unit to which it is mounted
(referred to as the local CPU Unit).

Note

(1) The SNTP (Simple Network Time Protocol) server is used to control the

time on the LAN.

(2) An error will occur in the following CPU Units when the automatic clock

adjustment function is executed under the conditions shown in the table.

(3) The manufacturing date can be determined from the lot number on the

side or top corner of the CPU Unit.

(4) The lot numbers are as follows:

YYMMDDnnnn, in which YY indicates the last two digits of the year, MM
the month, DD the day, and nnnn the serial number.

(5) In accordance with SNTP protocol specifications, automatic adjustment

will not be possible from February 7, 2036. In Ethernet Units, this function
will no longer operate from February 7, 2036 (this status will not be dis-
played as error information).

24: 00: 00

Intranet

SNTP server

Automatic clock adjustment

Ethernet

Ethernet Unit

Clock data is obtained from the
SNTP server and written at a particular
time ro when a designated bit turns ON.

The clock information can be broadcast
to other CPU Units on the same Network.

CPU Unit

Conditions

CPU Units manufactured on or
before January 31, 2003 (lot num-
bers 030131 or earlier):
CJ1G-CPU

@@

H

CJ1H-CPU

@@

H

CS1G-CPU

@@

H

CS1H-CPU

@@

H

When the CPU execution mode is set to other
than normal mode (priority peripheral servicing
mode, parallel processing with synchronous
memory access mode, or parallel processing
with asynchronous memory access mode).

AND

When the CPU Unit operating mode is set to
RUN or MONITOR mode.