107

Using Socket Service Functions

Section 6-5

6-5

Using Socket Service Functions

6-5-1

Procedure

6-5-2

Settings Required for Socket Service Function

The following settings must be made in the Unit Setup when using socket ser-
vices.

1.

Make the basic settings.

Refer to SECTION 2 Startup Procedure in the Operation Manual Construction of Networks.

2.

Use the CX-Programmer or Programming Console to make the socket service settings in the
socket service parameter areas 1 to 8 (m+18 to m+88) allocated in the DM Area.

Note: The first word m in the allocated DM Area = D30000 + (100

×

unit number)

3.

Select Transfer to PLC from the Options Menu, and then click the Yes Button. The Setup data
in the allocated DM Area will be transferred to the CPU Unit.

4.

Use one of the following methods to request socket services.

Manipulating Dedicated Control Bits

Turn each of the Socket Service Request Switches 1 to 8 in the CIO Area from OFF to ON.

Executing the CMND(490) Instruction

Send each of the socket service requests in FINS commands addressed to the Ethernet Unit.

CX-Programmer

Unit Setup Tab

Setting

Setting requirements

Page

Setup

Broadcast

Required.

108

IP Address

Optional

Sub-net Mask

Optional

IP Router Table

Optional (Set when Ethernet
Unit will communicate through
the IP router with a socket on
another IP network segment)

TCP/IP keep-alive

Optional (Change when the
default setting of 120 min is
unacceptable.)