1 ethernet unit communications services, 2 functions listed by purpose, Ethernet unit communications services – Omron CS CJ1W-ETN21 User Manual

Page 26: Functions listed by purpose

background image

2

Ethernet Unit Communications Services

Section 1-1

1-1

Ethernet Unit Communications Services

Note

When transferring data through the internet, a global IP address must be
acquired for the Ethernet Unit.

1-2

Functions Listed by Purpose

Service

Main functions

Counterpart device

Reference

Mail send function

Through intranet or
internet

Used to e-mail specified I/O memory
data or a file (up to 1 MB) from the
PLC to the computer automatically
when a preset condition is met.

Computer
(E-mail software)

SECTION 2 Mail
Send Function

Mail receive func-
tion

Used to perform operations in the PLC
from the computer, such as reading or
writing I/O memory data, backing up
data, changing the operating mode, or
transferring files (up to 1 MB).

Computer
(E-mail software)

SECTION 3
Receive Mail
Function

FTP server func-
tion

Through intranet or
internet (See note.)

Used to transfer large files between
the computer and PLC.

Computer
(FTP client software)

SECTION 4
FTP Server

Socket service
function

Used to transfer data between gen-
eral-purpose applications and the
PLC.

Computer
(General applica-
tions that do not use
FINS communica-
tions)

SECTION 6
Socket Services

Automatic clock
adjust function

Through intranet

Used to automatically adjust the PLC's
internal clock.

SNTP Server

SECTION 5
Automatic Clock
Adjustment
Function

FINS communica-
tions

Through intranet or
internet (See note.)

Used to access the PLC from a com-
puter (FINS application) or send mes-
sage communications from one PLC
to another.

Note The PLC can be accessed with

FINS message communications
even from a DHCP client com-
puter or computer with an
unspecified FINS node address.

Computer
(User-created FINS
communications
application)

SECTION 7
Using FINS
Communica-
tions to Create
Host Applica-
tions

Timing and

direction

User purpose

Communications

service

Method

Restrictions

User-specified tim-
ing, sent from com-
puter

Reading and writing
data in the CPU Unit's
I/O memory

Mail Receive
Function

IOMRead (I/O memory read) and
IOMWrite (I/O memory write) com-
mands

The maximum data
size is 6,000
words.

Changing the CPU
Unit's operating mode

ChangeMode command

---

Performing operations
on EM file memory or
a Memory Card
installed in the CPU
Unit

FileWrite, FileRead, FileDelete,
and FileList commands

The maximum data
size is 1 MB.

Backing up the user
program or parameter
area in the CPU Unit

UMBackup (User program backup)
and PARAMBackup (Parameter
area backup) commands

---

Reading or clearing
the error log in the
Ethernet Unit or CPU
Unit

ErrorLogRead and ErrorLogClear
commands

---

Sending a specific
FINS command to a
specific Unit

FinsSend command

---