CONDENSATE TRAP REMOVAL (Fig. 79)
Disconnect the 2 upper rubber condensate pipes (A). Remove
the pin (B) that secures the trap to the air box plate. Disconnect
the lower rubber condensate pipe (C) from the condensate trap.
Carefully remove the condensate trap. Replace in the reverse
order.
FLUE COLLECTOR AND FLUE THERMOSTAT REMOVAL (Fig.
80)
Unclip and remove the air chamber front and left side covers.
Locate and remove the screw (A) that secures the flue gas
analysis test point cover (B). Disconnect the silicon pipe (right
hand) of the blocked flue switch. Remove the clip (C) and the flue
thermostat (D). Gently pull down and to the left and ease the flue
collector from its location. Replace in the reverse order.
A
B
Fig. 80
Fig. 79
A
B
C
A
B
C
C
D
See also other documents in the category Raypak Water boiler:
- 240692 (31 pages)
- HIDELTA 992B (68 pages)
- 1000 (74 pages)
- RAYTHERM 962-1826 (2 pages)
- 335 (1 page)
- 504-2004 (4 pages)
- 265 (14 pages)
- 751-1501 (2 pages)
- HI DELTA HD401 (48 pages)
- DEL TA LIMITED 899B (5 pages)
- 2100 - 4001 (2 pages)
- H-0042B (4 pages)
- 2005 (8 pages)
- HI DALTA HD401 (48 pages)
- XFYRE 400 (8 pages)
- 42 & 66 (2 pages)
- 992BE (5 pages)
- 500 (56 pages)
- 182-400 (2 pages)
- Gas Fired Boiler (8 pages)
- MVB 5042004 (56 pages)
- B0147 (43 pages)
- RAYTHERM 0042B (40 pages)
- WH 0090A (28 pages)
- H7 504-2004 (2 pages)
- 503-2003 (60 pages)
- XFYRE NINETY PLUS 850 (8 pages)
- 0066B (38 pages)
- 195A (28 pages)
- Power Vent Raytherm 4001 (2 pages)
- FlexGas (1 page)
- XPAK 120 (12 pages)
- XTHERM 1505 (8 pages)
- RayTherm Commercial Boilers And Water Heater (4 pages)
- 0135B (6 pages)
- RayTemp Hot Water Energy Management Control (30 pages)
- 0090B (39 pages)
- B6000 (51 pages)
- B6000 (2 pages)
- 1001 (76 pages)
- RAYTHERM 133-4001 (44 pages)
- HI DELTA SS HD401 (4 pages)
- XFYRE 300-850 (2 pages)
- 30B (4 pages)