beautypg.com

Raypak XPAK 85 User Manual

Page 55

background image

55

CONDENSATE TRAP REMOVAL (Fig. 79)
Disconnect the 2 upper rubber condensate pipes (A). Remove
the pin (B) that secures the trap to the air box plate. Disconnect
the lower rubber condensate pipe (C) from the condensate trap.
Carefully remove the condensate trap. Replace in the reverse
order.

FLUE COLLECTOR AND FLUE THERMOSTAT REMOVAL (Fig.
80)
Unclip and remove the air chamber front and left side covers.
Locate and remove the screw (A) that secures the flue gas
analysis test point cover (B). Disconnect the silicon pipe (right
hand) of the blocked flue switch. Remove the clip (C) and the flue
thermostat (D). Gently pull down and to the left and ease the flue
collector from its location. Replace in the reverse order.

A

B

Fig. 80

Fig. 79

A

B

C

A

B

C

C

D