Raypak XPAK 85 User Manual

Page 11

background image

11

XPak 85 XPak 120

Boiler flue gas connection

in

2 3/8

2 3/8

mm

60

60

Combustion air connection outer dia.

in

4

4

mm

100

100

Free fan unit feed pressure

in w. c.

0.26

0.18

Pa

65

45

Flue gas mass flow rate at rated full load (A)

lbs/hr

90.39

123.17

kg/hr

41

55.87

Flue gas mass flow rate at rated full load (E)

lbs/hr

88.89

121.18

kg/hr

40.32

54.97

Flue gas mass flow rate at rated partial load (A)

lbs/hr

26.58

28.48

kg/hr

12.06

12.92

Flue gas mass flow rate at rated partial load (E)

lbs/hr

25.08

27.99

kg/hr

11.88

12.70

Condensate flow rate (A) at max - 122/86 °F (50/30°C) USG/hr

0.37

0.41

ltr/hr

1.41

1.56

Condensate flow rate (A) at min. - 122/86 °F (50/30°C) USG/hr

0.13

0.16

ltr/hr

0.48

0.6

Flue temperature at boiler return temp. 86°F/30°C

°F

186.0

170.0

at full load (A)

°C

86.0

77.0

Flue temperature at boiler return temp. 86°F/30°C

°F

163.0

165.0

at partial load (A)

°C

73.0

74.0

Flue temperature at boiler return temp. 140°F/60°C

°F

194.0

186.0

at full load (A)

°C

90.0

86.0

Max flues length de-rate less 2%
Max length horizontal coaxial 60/100 mm

ft

6.5

6.5

m

2

2

Max total length 2 pipe 3” (80 mm) (air + flues)

ft

40+40

16+16

m

12+12

5+5

Max flues length de-rate less 5%
Max length horizontal coaxial 60/100 mm

ft

26

26

m

7.8

7.8

Max total length 2 pipe 3” (80 mm) - (air + flues)

ft

130+130

115+115

m

40+40

35+35

Minimum Clearances To Combustibles
Top - front - rear

in

0 - 0 - 0

mm

0 - 0 - 0

Left - right - vent pipe

in

0 - 0 - 0

mm

0 - 0 - 0

Recommended Minimum Service Clearances
Top - front - rear

in

12 - 24 - 0

mm

300 - 600 - 0

Left - right

in

1 - 1

mm

25 - 25

Pipe Connections
Gas supply connection (shut off valve)

in

3/4 NPT - female

Boiler in connection

in

3/4 NPT - male

Boiler out connection

in

3/4 NPT - male

Pressure relief valve

in

3/4 NPT - female

Condensate connection diameter (rubber flexible)

in

0.825 female

mm

21 female

Boiler drain valve - open-ended wrench dimension

in

7/16

mm

11

Boiler Dimensions And Weight
Height x Width x Dept

in

30.7 x 15.75 x 14.1

30.7 x 17.7 x 14.1

mm

780 x 400 x 358

780 x 450 x 358

Weight net

lbs

73

80

kg

33

36

Components
Burner

Stainless Steel

Main heat exchanger

ASME approved extruded aluminum

Gas valve

SIT 848

Pump

Groundfos UPM 15-52

Groundfos UPM 15-62

Pressure relief valve

Watts M350 - M2 ASME approved

Fan

MVL RG 128

3-way valve for DHW tank (field supply)

Honeywell VC6011 + VCZMK6000

Injector Natural Gas (A) Ø

0.20 inch (5.1 mm)

0.26 inch (6.7 mm)

Injector LPG (E) - black coated Ø

0.15 inch (3.9 mm)

0.19 inch (5.0 mm)

notes
*See jumpers configurations for heating temperature range setting
**If the gas supply pressure exceeds the maximum gas supply pressure value, a separate gas pressure regulator must be installed
upstream of the heating system.