TECHNICAL DATA

Tab. 1

XPak 85

XPak 120

Input - Output
Input - (0 - 2000 ft / 0 - 610 m)

Btu/hr

25,600 - 87,000

27,300 - 119,500

kW

7.5 - 25.5

8.0 - 35.0

Input - (2000 - 4500 ft / 610 - 1375 m)

Btu/hr

25,600 - 82,900

27,300 - 114,300

kW

7.5 - 24.3

8.0 - 33.5

Output (176°F - 86°F / 80°C - 30°C)

Btu/hr

25,200 - 76,600

26,600 - 108,300

kW

7.4 - 22.5

7.8 - 31.7

Energy Guide
AFUE

%

91.8

92.6

Gas
Gas supply pressure Natural Gas (A)

in w. c.

6.82

kPa

1.70

Min. gas supply pressure Natural Gas (A)

in w. c.

3.5

kPa

0.87

Max. gas supply pressure Natural Gas (A)**

in w. c.

10.5

kPa

2.62

Gas supply pressure LPG (E)

in w. c.

11

kPa

2.75

Min. gas supply pressure LPG (E)

in w. c.

8

kPa

1.99

Max. gas supply pressure LPG (E)**

in w. c.

13

kPa

3.24

Gas Rate max natural gas (A)

ft3/hr

87.77

121.01

sm3/hr

2.49

3.43

Gas Rate min natural gas (A)

ft3/hr

26.14

28.01

sm3/hr

0.74

0.79

Gas Rate max LPG (E)

lbs/hr

4.02

5.55

kg/hr

1.82

2.52

Gas Rate min LPG (E)

lbs/hr

1.20

1.28

kg/hr

0.54

0.58

System Data
Minimum relief valve capacity

lbs/hr

87

119.50

Maximum operating pressure

p.s.i.

45

bar

3.1

Minimum operating pressure

p.s.i.

6.52

bar

0.45

Recommended system pressure

p.s.i.

15

bar

1

Boiler max flow rate (ltr/hr)

GPM

5.72

6.2

ltr/hr

1,300

1,400

Pump residual head at max flow rate

in w. c.

60.22

44.11

mbar

150

110

Primary water content

CAN G

0.70

0.84

USG

0.85

1.0

ltr

3.2

3.8

Boiler Water Temperature
Adjustable high limit range - high temp. (radiators heating)* °F

104 - 176

°C

40 - 80

Adjustable high limit range - low temp. (space heating)*

°F

68 - 113

°C

20 - 45

DHW production - set point

°F

95 - 140

°C

35 - 60

Max boiler temperature

°F

194

°C

90

Electric Data
Electric rate voltage

V - Hz

120 - 60

Current less than

A

1.19

1.25

Electric consumption (pump included)

W

133

141

Electrical protection rating

IP

IPX5D

Fuses

A - VAC

4 - 250

Flue Gas Values
CO2 setting natural gas (A)

%

8.5%

CO2 setting LPG (E)

%

10.0%

NOx @ max (A)

ppm

< 20

< 20

NOx @ min (A)

ppm

< 15

< 15

CO @ max (A) without air

ppm

< 135

< 170

CO @ min (A) without air

ppm

< 15

< 25

NOx @ max (E)

ppm

< 20

< 20

NOx @ min (E)

ppm

< 15

< 20

CO @ max (E) without air

ppm

< 200

< 220

CO @ min (E) without air

ppm

< 40

< 35