beautypg.com

Banned material statement, Manual handling statement, Principle components – Raypak XPAK 85 User Manual

Page 12: Mode of operation (at rest), Mode of operation, Safety devices

background image

12

BANNED MATERIAL STATEMENT:

No banned materials or substances have been used in the
manufacture or production of this appliance or its inherent
components

MANUAL HANDLING STATEMENT:

CAUTION:

This appliance may require 2 or more persons

to lift or carry it to the installation location; due to the weight
of the appliance it may be necessary for two people to lift
and attach the appliance to its mounting. To avoid the
possibility of injury during the installation, servicing or
cleaning of this appliance, care should be taken when
handling component edges.

pressure

relief

valve

pump

return

temperature

sensor

main heat

exchanger

bottom

auto air

valve

pressure

switch

Heating

return

automatic

bypass

Heating

flow

drain

valve

flow

temperature

sensor

top

auto air

valve

manual air

release

pressure

relief valve

X P A K I N T E R N A L H Y D R A U L I C
CIRCUIT (FIG. 2)

Fig. 2

PRINCIPLE COMPONENTS

A fully integrated electronic control board featuring electronic
temperature control, anti-cycle control, pump over-run, actuator
anti-block function, self-diagnostic fault indicator, full air/gas
modulation.
- Radial aluminum heat exchanger.
- Electronic ignition with flame supervision
- Integral pump
- Fan
- Water pressure switch
- Condensate level sensor
- Pressure gauge
- Pressure relief valve
- Flue thermostat
- Flue sensor
- Blocked flue switch

MODE OF OPERATION (AT REST)

When the appliance is at rest and there are no requests for heating
or hot water, the following functions are active:
- 2-stage freeze protection system – the freeze protection system

protects the appliance against the risk of freeze damage. The
first stage enables activation of the pump should the tempera-
ture of the appliance fall to 43°F (6

o

C). Should the first stage

become active, the appliance will function on minimum +25%
power until it reaches 95°F (35

o

C).

- Anti-seize function – the anti-seize function enables the pump

to be energized for short periods, when the appliance has been
inactive for more than 24-hours.

MODE OF OPERATION

When there is a request for heat and/or hot water, via the
programmer/time clock and/or any external control, the pump and
fan are started, the fan speed will modulate until the correct signal
voltage is received at the control PCB. At this point an ignition
sequence is enabled.
Ignition is sensed by the electronic circuitry to ensure flame
stability at the burner. Once successful ignition has been
achieved, the electronic circuitry increases the gas rate to 75% of
the MAX Heating (set by the corresponding HTG trimmer) for a
period of 15 minutes. Thereafter, the boiler’s output will either
increase to maximum or modulate to suit the set requirement.
When the appliance reaches the desired temperature the burner
will shut down and the boiler will perform a three-minute post purge
(timer delay).
When the request for heat has been satisfied the appliance pump
and fan may continue to operate to dissipate any residual heat
within the appliance.

SAFETY DEVICES

When the appliance is in use, safe operation is ensured by:
- a water pressure switch that monitors system water pressure

and will de-activate the pump (when lockout condition is
reached), fan and burner should the system water pressure
drop below the rated tolerance;

- blocked flue switch that monitors flue pressure and will de-

activate the pump (when lockout condition is reached), fan and
burner should the flue pressure increase over the rated tolerance;

- fan speed sensor to ensure safe operation of the burner;
- a high limit thermostat that over-rides the temperature control

circuit to prevent or interrupt the operation of the burner;

- flame sensor that will shut down the burner when no flame signal

is detected;

- a sensor that interrupts the operation of the appliance if the

condensate pipe becomes blocked;

- a pressure relief valve which releases excess pressure from the

primary circuit;

- a flue sensor that controls the flue temperature continuously

checking to be right according the output;

- a flue thermostat that over-rides the temperature control circuit

to prevent or interrupt the operation of the burner.