Roberts Gorden Vantage TF-Series User Manual
Page 8
ROBERTS GORDON
®
T F-S
E RIE S
S
U BMI TT AL
S
HEE T
© 2004 Roberts-Gordon
APPLI CAT IONS, ENGIN EE RING AND DE TAI LE D GUIDANCE ON SYST EMS DE SI GN, I NSTALL ATION AND PRODUCT PE RFORMANCE I S AVAIL ABL E UPO N REQUE ST. ROBERTS GO RDON
®
PRODUCTS ARE TO BE
INSTAL LE D ONLY I N ACCOR DANCE WIT H L OCAL L AW S, CODES AND RE GULAT IONS, AND ONLY BY A CONTRACTO R QUALI FIE D IN THE INST AL LAT ION AND SE RVICE OF GAS-F IRE D HEAT ING E QUIPMEN T.
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.
45
°
Tilt Reflector
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
TF-120
8
8
60
54
21
21
153
138
TF-160
8
8
66
60
21
21
168
153
TF-200
10
8
74
64
26
21
188
163
TF-250
10
8
78
69
26
21
199
176
TF-300
12
8
84
74
31
21
214
188
TF-350
12
8
85
79
31
21
216
201
TF-380
12
8
85
79
31
21
216
201
A
C
D
B
U-Tube, Standard Reflector
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
TF-120
6
35
63
30
16
89
161
77
TF-160
6
38
69
37
16
97
176
94
TF-200
6
40
76
39
16
102
194
100
TF-250
6
46
79
43
16
117
201
110
TF-300
6
50
84
47
16
127
214
120
TF-350
8
54
87
51
21
138
221
130
TF-380
8
54
87
51
21
138
221
130
A
C
D
B
U-Tube, Full 45
°
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
TF-120
8
8
60
42
21
21
153
107
TF-160
8
8
66
46
21
21
168
117
TF-200
8
8
74
52
21
21
188
133
TF-250
8
8
78
61
21
21
199
155
TF-300
8
8
84
66
21
21
214
168
TF-350
8
8
85
70
21
21
216
178
TF-380
8
8
85
70
21
21
216
178
B
C
D
A