FLUE EXTENSION KITS

CAUTIONS

1. Maximum extendable length

FOR BEST ROOM AIR HUMIDITY, KEEP
WATER IN THE HUMIDIFIER TRAY.

2. To prevent water condensation

Condensed water
may accumulate
here, and cause a blockage
preventing combustion.

7.0 Metres less 1m per bend to a max 3

bends.

• The bend where the hose and pipes leave

the body is not counted.

• The air intake hose should run along the

exhaust pipe.

3. Condensed water formed by combustion, will

run back to the unit, and may overflow from the
condensation pan if pipes are longer than 2.0
metres
. Therefore, pipes exceeding these
lengths should be made to drain to the outside
by giving their horizontal portions 3˚ or more
downward and outward slope.

CAUTION
Never allow the exhaust pipe to sag, as
condensed water may accumulate and
cause incomplete combustion.

3 slope(approximate)

Less than 2.0m

4. Wherever the air intake hose and exhaust pipe

run sideways, try to have the exhaust pipe on
top (to prevent the air intake hose from sagging
onto the exhaust pipe.)

Exhaust pipe

Exhaust pipe

Air intake hose

Air intake hose