Nh electric steam humidifier – Nortec 132-3091 User Manual
Page 29
- 26 -
Humidifier Mandatory Pre Start-up Checklist (p. 1 of 1)
Unit Serial #: _ _ _ _ _ _ _ _
# of humidifiers: _____ Tag:_____________
Unit type:
Voltage: _____V/___ph Steam output: ____lbs/hr
Customer/Job:_______________ Address: __________________________________
Inspected by: ________________ Date of inspection:____/____/____
_____________________________________________________________________________________________
WATER QUALITY:
Well water
r
City water r
Softened wate r
RO / DI water
r
Conductivity: _______mhmos
Hardness: _____ gr.
HUMIDIFIER MOUNTING:
Clearances around the unit
Acceptable
Obstruction
- Front (door opens freely?)
3ft min
____________________
- Top (steam lines)
2ft min
____________________
- Bottom (fill, drain, controls) 2ft min ____________________
- Right (main pwr)
2ft min ____________________
STEAM LINES:
CONDENSATE LINES:
- Slope up 2” per 12”
r
- Slopped back to drain
r
- Slope down ½” per 12”
r
- Trapped 2” more than static duct pressure
r
- Traps r
- Size _______
- Insulated
r
- Stainless steel
r
or plastic
r
- Length/Size _____/_______
- ________% Vertical _______% Horizontal
- 90 deg. elbows
r
qty: ____
- 45 deg. Elbows
r
qty: ____
- Can condensate be trapped anywhere in the steam line? Yes
r
no
r
WATER LINES:
- ½” at max 4ft from the unit
r
- 3/8” connection at fill
r
- water pressure: 30-80psig
r
- PVC
r
- Stainless steel
r
DRAIN LINES:
- Air gap located within 3ft of the unit
r
- Slopped to drain
r
- Size:________
CYLINDER:
- Cylinder properly installed and sitting upright
WIRING:
- No loose wires around the unit or on the PC board? yes
r
no
r
CONTROLS:
Installed Location / Wiring /Setting
Installed Location / Wiring /Setting
- High limit:
r
___________________
- Air proving:
r
___________________
- Mod controller:
r
___________________
- Other:
r
___________________
POWER:
- Voltage, amperage rating and fuse correspond to Spec Label
r
- Disconnect switch located close to humidifier
r
NH Electric Steam Humidifier