high water sensor board has a primary voltage side.

One leg connects to the primary leg; one leg connects

to the short sensor pin in the top of the cylinder. A

potential, somewhat less than primary, is picked up by

the sensor at high water level, which “makes” the

red/black circuit on the low voltage side. This creates

a resistive loop across terminals 2-4 on the electronics

which stops the fill valve until water boils down below

the sensor pin.

Back at the electronics, the contactor receives its

“hot leg” from terminal 12. The fill receives its “hot leg”

from terminal 14. The drain receives its “hot leg” from

terminal 16. Unlike the contactor and fill, the drain

gets its “ground leg” directly from the transformer. It

does not depend on the air proving switch to activate.

The yellow and green status lamps are LED’s.

Polarity is important. Terminal 26 is positive dc

supply. Terminal 22 and 24 are switched dc grounds

for yellow and green respectively.

BLOWER PACKS

An optional blower pack (BP), if present, gets its

primary voltage from inside the humidifier. This way,

only one external power source has to be connected to

the equipment.

TERMS USED

RATED AMPS: Refers to amps listed on the

humidifier specification label.

SHORT CYCLING: When the ‘on time’ of the

humidifier is less than ten minutes upon a call for

humidity. To correct short cycling, all humidifiers have

a capacity adjustment which allows the output of the

humidifier to be reduced as low as 20% of rated

output, thus extending the ‘on time’ required to

maintain output.

FOAMING: The phenomenon which can occur in

water when the impurities, already in the water, reach

an excess concentration as result of boiling away pure

water and the continued boiling action agitating the

contained water. The humidifier electronics are

designed to prevent this occurrence although in

extreme cases water will foam with little concentration,

making it necessary to have the drain time of the

water, contained in the cylinder, increased. Foaming

is normally caused by short cycling, a restricted drain,

or back pressure. The foam, generated in these

instances, is conductive and may lead to a false full

cylinder indication if the level of the foam approaches

the top of the cylinder.

BACK PRESSURE: Restriction of steam flow

caused by long steam runs, improperly sloped steam

lines, elbows changing the direction of the steam flow

from horizontal to vertical without a drain leg, any

plumbing detail allowing the accumulation of

condensate, undersized steam line, improper steam

distributor, downward air flow onto the distributor

creating excess static pressure at the steam outlets or

high static pressure ducts (not probable). To

overcome excess static pressure in the duct, a fill cup

extension kit should be used. In downflow

applications, a downflow distributor should be used but

in some cases the fill cup extension will also be

required.

RESET UNIT (HUMIDIFIER): To reset the

humidifier, the on/off/drain switch at the front of the

humidifier should be switched to the off position for a

minimum of five seconds and then switched back to

the on position.

MONITORED LEG: Refers to the primary wire, to

the cylinder, which loops through the current sensing

device on the main pcb. This wire is terminated at the

red cylinder plug at the cylinder. Units with six primary

wires to the cylinder will monitor only one of the two

wires, terminating with red plugs.