- 12 -
NHMC
UNIT STATUS LAMPS
REMOTE INDICATION (24 VAC TO:)
SYSTEM MESSAGE
DISPLAYED ON LCD
UNIT
CONTACTOR YELLOW
GREEN
61-20
“YELLOW”
62-40
“GREEN”
63-36
“RED”
Maximal Level
ON
ON
ON
OFF
ON
OFF
Excess Current / Error 1
OFF
ON
OFF
ON
OFF
OFF
No Current / Error 2*
OFF
ON
OFF
ON
OFF
OFF
Max. Filling Time / Error 3
OFF
ON
OFF
ON
OFF
OFF
Cylinder Spent / Error 4
ON
ON
ON
OFF
ON
ON
No Current / Error 5
OFF
ON
OFF
ON
OFF
OFF
Output Too Low / Error 6
OFF
ON
OFF
ON
OFF
OFF
Electronic / Error 7
OFF
ON
OFF
ON
OFF
OFF
Phase Interrupt / Error 8
ON
ON
OFF
OFF
OFF
OFF
Cyl. Lifespan End / Error 9
OFF
ON
OFF
ON
OFF
ON
* When No Current/Error 2 is displayed, display will change to show Maximal Level and will alternate back and forth.
NHP
UNIT STATUS LAMPS
REMOTE INDICATION
(24 VAC TO:)
SYSTEM FAULTS*
UNIT CONTACTOR
YELLOW
GREEN
“YELLOW” 61-20
Maximal Level
See NHMC Chart above for details
Excess Current
OFF
ON
OFF
ON
No Current
OFF
ON
OFF
OFF
Max. Filling Time
OFF
ON
OFF
ON
Cylinder Spent
ON
FLASHING
ON
OFF
No Current
OFF
ON
OFF
OFF
Output Too Low
OFF
ON
OFF
OFF
Electronic
N/A
N/A
N/A
N/A
Phase Interrupt
N/A
N/A
N/A
N/A
Cyl. Lifespan End
OFF
FLASHING
OFF
ON
*NOTE: NHP does not display actual message or error.
- Remote indication 61-20 “yellow” means humidifier has shutdown and one of several system messages is showing.
The exception is on the NHP when No Current or Output Too Low is the fault, 61-20 “yellow” will be off, but the yellow
light on the NHP will be on.
- Remote indication 62-40 “green” means contactor is on; humidifier is operating.
- Remote indication 63-36 “red” means cylinder is spent; replacement is necessary.
Figure #13
System Messages and Responses (EPROM : 2.XXN)