beautypg.com

Nortec 132-3091 User Manual

Page 20

background image

Response: See Figure #2, NHMC/NHP System

Messages

4. Max. Filling Time - Error 3

Symptom(s) Diagnosed: Time dependent.

Neither Maximal Level (full cylinder) is detected,

nor is there enough current drawn to meet

capacity demand. Current monitored on primary

lead to cylinder is greater than zero and not

decreasing. The unit will have tried to self-correct

prior to system shutdown by pulse activating the

drain valve to possibly clear any debris holding the

drain valve open.

Probable Cause(s):

1.

Steam line restriction causing back pressure.

2.

Improper fill rate.

3.

Leaking drain valve

4.

Full cylinder not detected.

Unit Takes Self-Corrective Action: Yes. It

pulse-activates the drain valve to possibly clear

any dirt. It retests. If the symptoms persist after

two attempts, it then responds as shown in Figure

#2.

Corrective Action:

1.

Check for water leaking from drain. If present,

correct the drain valve deficiency (check for debris

holding drain coil plunges open).

2.

Ensure the steam line, from the cylinder outlet to

the steam distributor (duct or blower pack), is

properly installed, to ensure back pressure is not

the case.

3.

Check water level in cylinder.

4.

If full reset unit and ensure there is a demand for

steam (the green LED on unit door will stay

illuminated. Maximal Level should be indicated on

the LCD display and both green and yellow LED is

on the unit door illuminate almost immediately. If

Maximal Level is not indicated, a problem exists

with the high water sensor circuitry.

a) Check wiring of the high water sensor PCB

(refer to unit wiring diagram).

b) Check for amperage on all wires at the

cylinder, with an amp probe (amp clamp). If
amperage is not detected on all wires,
correct primary wiring deficiency. If
amperage is detected on all wires, proceed
to next step.

c) Place a jumper across 42 and 48 of main

PCB for five seconds. If Maximal Level is not

displayed and the fill valve does not energize (green
LED must be illuminated), the main PCB is defective.
If Maximal level is displayed, a problem exists with
the cylinder or the high water sensor PCB. A voltage
of 85 VAC or greater across the orange wires of the
high water PCB ( one orange wire terminates at the
white sensor plug attached to the soldered pin of the
cylinder, the other terminates at one of the contactor
connections) will signal a full cylinder (Maximal
Level) to the main pcb. If this voltage does exist, the
problem is with the high water PCB, if not, the
problem is within the cylinder (can be caused by
cylinder being past end of life.

5.

If not full, drain cylinder, reset unit, and check the

fill rate (refer to Figure #2 ). If the fill rate is

correct, back pressure is the likely cause and

should be rechecked.

Response: See Figure #2, NHMC/NHP System

Messages.

5. Cylinder Spent - Error 4

Symptom(s) Diagnosed: Water level stays high,

cycling on and off Maximal Level (full cylinder),

without an increase in output/amp draw or

reaching demand.

Probable Cause(s):

1.

Cylinder has reached end of life due to insulative

mineral coating on electrodes.

2.

New cylinder start up with low incoming water

conductivity.

Corrective Action:

1.

If the cylinder is not new, replace the cylinder

immediately. Within approximately three days, the

unit will shut itself down on Error 9 resulting in no

output instead of reduced output.

2.

If the cylinder is new, the electronics will

differentiate cylinder spent from new cylinder start

up and the displayed error will discontinue without

a shutdown on Error 9.

Response: See Figure #2, NHMC/NHP System

Messages.

6. No Current - Error 5

Symptom(s) Diagnosed: Time dependent. No

current sensed by the electronics on the monitored

primary lead to the cylinder. The unit will have

tried to self correct prior to system shutdown by

pulse activating the drain valve, to possibly clear

any debris holding the drain valve open.

Probable Cause(s):

- 17 -