beautypg.com

Nortec 132-3091 User Manual

Page 21

background image

1.

No current being drawn on the monitored primary

lead to the cylinder, or the actual current is not

being sensed.

2.

Water does not reach the electronics due to a

restricted water supply line or due to a constantly

open/leaking drain valve preventing a water level

increase.

3.

High duct static pressure blowing back into the fill

cup (via steam line, empty cylinder) diverting the

fill cup water to the overflow.

Unit Takes Self-Corrective Action: Yes. It

pulse-activates the drain valve to possibly clear

any dirt holding the seal open. It re-tests. If

symptoms persist after two attempts, it then

responds as shown in Figure #2.

Corrective Action:

1.

Check the water level in the cylinder.

2.

If there is water in the cylinder (1/5 of a full

cylinder or more) check monitored primary lead to

the cylinder for current with an amp clamp.

a) If current is present with zero output

indicated on the display, the problem is with
the main PCB.

b) If no current is present determine the cause

of the primary voltage interruption.

3.

If there is little or not water in the cylinder turn the

unit off and disconnect the steam line at the

cylinder. Reset the unit and monitor filling.

a) If unit fills and Error 5 does not reoccur, the

problem was likely caused by air flow through
the fill system and can be permanently
corrected by installing a U trap on the fill line
between the fill cup and the drain valve body.

b) If unit does not fill, then turn the unit off and

clean and check the drain valve (refer to
section on Mandatory Cleaning of the Drain
Valve in this manual) to ensure that there are
no obstructions or leaks in the drain valve
preventing it from holding water in the
cylinder, and check water inlet for
obstructions.

4.

Turn unit back on and see if it will fill.

a) If unit still does not fill, then with the unit

turned on, check for 24 VAC across the fill
valve (there must be a call for humidity).

b) If 24 VAC is present, then the problem is with

the fill valve.

c) If 24 VAC is not present, then check for 24

VAC across 6 and 14 on the PCB.

d) If 24 VAC is not present across 6 and 14 of

the PCB, then the problem is with the main
PCB.

e) If 24 VAC is present across 6 and 14 of the

PCB, then check for a break in the circuit to
the fill valve.

Response: See Figure #2, NHMC/NHP System

Messages.

7. Output Too Low - Error 6

Symptom(s) Diagnosed: Time dependent.

Neither Maximal Level (full cylinder) is detected,

nor is there enough current drawn to meet

capacity demand. Current monitored on primary

lead to cylinder greater than zero but decreasing.

Unit Takes Self-Corrective Action: Yes. It

pulse-activates the drain valve to possibly clear

any dirt holding the seal open. It re-tests. If

symptoms persist after two attempts, it then

responds as shown in Figure #2.

Probable Cause(s): Refer to Error 3.

Corrective Action: Refer to Error 3.

Response: See Figure #2, NHMC/NHP System

Messages.

8. Electronic - Error 7 (NHMC only)

Symptom(s) Diagnosed: The electronics of the

main PCB have diagnosed the main PCB as

defective.

Probable Cause(s):

1.

A spike in the primary power supply to the

humidifier, either high (surge) or low (brown out),

causing the electronics to experience a logic

glitch.

2.

A problem with the main PCB.

Corrective Action:

1.

Reset humidifier and monitor display. If Error 7

reoccurs within one minute of resetting the unit,

the problem is with the main PCB. If Error 7 is not

repeated, the primary power to the unit is suspect.

Response: See Figure #2, NHMC System

Messages.

- 18 -