14.1.1. Relationship between the condition of the air conditioner and pressure and
electric current
Cooling Mode
Heating Mode
Condition of theair
conditioner
Low Pressure
High Pressure
Electric current
during operation
Low Pressure
High Pressure
Electric current
during operation
Insufficient refrigerant
(gas leakage)
Clogged capillary tube
or Strainer
Short circuit in the
indoor unit
Heat radiation
deficiency of the
outdoor unit
Inefficient compression
•
Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
14.1.2. Diagnosis methods of a malfunction of a compressor and 4-way valve
Natureof fault
Symptom
•
•
Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor
•
•
The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C [158 to
194°F]).
•
•
The difference between high pressure and low pressure becomes almost zero.
•
•
Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
•
•
Thecompressor is a humming sound.
•
•
Electric current during operation becomes approximately 80% lower than the normal value.
Insufficient switches of the 4-way valve
•
•
The temperature different between from the discharge tube to the 4-way valve and from
suction tube to the 4-way valve becomes almost zero.