Outdoor Unit
• To protect compressor from reverse
rotation when there is a instantaneous
power failure.
60 Secs. Forced Operation Control
• Once the compressor is activated, it
does not stop within the first 60 secs.
However, it stops immediately with
remote control stop signal.
Overload Protector
• OLP to protect the compressor. Overload
Protector will trip when
– High temperature or high current flows
to compressor.
Compressor Reverse Rotation
Protection Control
Outdoor Fan Operation Control
• Temperature Fuse.
4-Way Valve Control
• When the unit is switched to “OFF”
during Heating Operation, 4-way valve
stays at Heating position for 5 minutes.
Overload Protection Control
• Outdoor fan stops when indoor heat
exchanger temperature rises to 51°C
(123.8°F) and above, and restarts when
the indoor heat exchanger temperature
drops to 49°C (120
.
2°F) and below.
• Compressor stop when indoor heat
exchanger temperature reaches 65°C
(149°F) or above. (Heating Operation
Only)
Deice Control
• To prevent frosting at outdoor heat
exchanger. (Only for Heating Operation)
• Temperature of outdoor heat exchanger
is sensed by TRS (Thermal Reed Switch).
TRS OFF temperature 4°C (39.2°F).
TRS ON temperature -3°C (26.6°F).
Compressor Protection Control
• If the outdoor fan motor is not running
after compressor starts for 50 secs.,
compressor will stop. (Cooling and Soft
Dry Operation only).
Low Ambient Temperature Control
• To protect air conditioner from damage
under the low outdoor ambient
temperature < -10°C (14°F).