Outdoor Unit

• To protect compressor from reverse

rotation when there is a instantaneous
power failure.

60 Secs. Forced Operation Control

• Once the compressor is activated, it

does not stop within the first 60 secs.
However, it stops immediately with
remote control stop signal.

Overload Protector

• OLP to protect the compressor. Overload

Protector will trip when
– High temperature or high current flows

to compressor.

Compressor Reverse Rotation
Protection Control

Outdoor Fan Operation Control

• Temperature Fuse.

4-Way Valve Control

• When the unit is switched to “OFF”

during Heating Operation, 4-way valve
stays at Heating position for 5 minutes.

Overload Protection Control

• Outdoor fan stops when indoor heat

exchanger temperature rises to 51°C
(123.8°F) and above, and restarts when
the indoor heat exchanger temperature
drops to 49°C (120

.

2°F) and below.

• Compressor stop when indoor heat

exchanger temperature reaches 65°C
(149°F) or above. (Heating Operation
Only)

Deice Control

• To prevent frosting at outdoor heat

exchanger. (Only for Heating Operation)

• Temperature of outdoor heat exchanger

is sensed by TRS (Thermal Reed Switch).
TRS OFF temperature 4°C (39.2°F).
TRS ON temperature -3°C (26.6°F).

Compressor Protection Control

• If the outdoor fan motor is not running

after compressor starts for 50 secs.,
compressor will stop. (Cooling and Soft
Dry Operation only).

Low Ambient Temperature Control

• To protect air conditioner from damage

under the low outdoor ambient
temperature < -10°C (14°F).