Hamilton Sundstrand Company ACT2000 User Manual
Page 57
Symptom
Probable Causes
Corrective Action
FAULT alarm
Various
Upload Fault File to identify source of fault
OVER TEMP alarm
Ambient temperature limit
exceeded
Electronics or motor winding
temperature out of range
Allow actuator to cool and re-start
Reduce ambient temperature
Check for jammed extension rod
FAULT and OVERTEMP
alarm
No 120 VDC Power
DSP Failure
Ensure 120 VDC at actuator
Contact factory
Table 5-2. ACT2000 In-Service Troubleshooting Chart
For troubleshooting purposes, use Table 5-3 to verify the actuator
electrical continuity integrity.
Disconnect the ACT2000 power and digital harness connectors and use a
digital multi-meter (DMM) to check the resistance values between the
wires indicated on the table. If an open circuit is detected, send the
ACT2000 to Precision Engine Controls Corporation for test and repair.
WARNING – Shock Hazard
Remove all power to the ACT2000 prior to continuity check.
Function
Actuator Wire Colors
Resistance Value
DEMAND
BRN and WHT/BRN
225
Ω
RUN
VIO and WHT/VIO
4.7 K
Ω
RESET GRY
and
WHT/GRY
4.7 K
Ω
POWER
RED and GREEN
High Impedance, but
not open circuit.
MOTOR CURRENT
BLU and WHT/BLU
High Impedance
POSITION
YEL and WHT/YEL
High Impedance
FAULT Alarm
ORN and WHT/ORN
High Impedance
OVERTEMP Alarm
BLK and WHT/BLK
High Impedance
Table 5-3. ACT2000 Electrical Continuity Troubleshooting Chart
CH. 4: TROUBLESHOOTING THE ACT2000
51