ACT2000 USER GUIDE

Symptom

Probable Causes

Corrective Action

Actuator Inoperative -
FAULT alarm

Power Wires not connected

No or low 120 VDC power

Ensure RED and GREEN wires correctly connected to
Actuator
Ensure 120 VDC Primary System Power at Actuator

Actuator Inoperative -
NO FAULT alarm

No RUN or position command

Ensure VIOLET and WHITE/VIOLET wires correctly
connected to Actuator
Ensure 24 VDC RUN and position command at
Actuator

Actuator moves toward
HOME then stops

Intermittent RUN command

Homing Force Too Low
No position demand

Ensure consistent 24 VDC RUN and position command

Ensure position command at actuator

Actuator moves toward
HOME intermittently

Intermittent RESET command

Ensure GRAY and WHITE/GRAY wires correctly
connected to Actuator
Ensure consistent 24 VDC RESET command

Actuator finds HOME then
moves to STOP position

No position demand signal

Ensure BROWN and WHITE/BROWN wires correctly
connected to Actuator
Ensure position demand > 2.0 mA at Actuator

Actuator does not track
position demand

No position demand signal

Ensure BROWN and WHITE/BROWN wires correctly
connected to Actuator
Ensure position demand > 4.1 mA at Actuator

Actuator does not hold
consistent position-oscillates
or dithers

Varying position demand signal

Ensure stable position demand at the actuator

No position feedback

Position feedback wires not
connected
No or low 120 VDC power
Actuator auto shut down

Ensure YELLOW and WHITE/YELLOW wires correctly
connected
Ensure 120 VDC at Actuator
Upload Fault File- check for motor windings over -
temperature faults.
Check for jammed extension rod

No motor current feedback

Motor current wires not
connected
No or low 120 VDC power

Ensure BLUE and WHITE/BLUE wires correctly
connected

Actuator Operative- FAULT
alarm active

Open circuit

Internal FAULT

Ensure ORANGE and WHITE/ORANGE wires
correctly connected to Actuator
Upload Fault File to identify source of fault

Actuator Operative- OVER
TEMP alarm active

Open circuit

Electronics or motor winding
temperature out of range

Ensure BLACK and WHITE/BLACK wires correctly
connected to Actuator
Reduce External ambient temperature
Check for jammed extension rod

RS232 Interface Inoperative Incorrect wiring




No or low 120 VDC power
COM1 not connected

Ensure WHITE/ORANGE/YELLOW,
WHITE/ORANGE/BLUE, WHITE/ORANGE/GREEN
wires correctly connected to Actuator and laptop PC.

Ensure 120 VDC Primary System Power at Actuator
Check laptop/PC com port

Table 5-1. Initial Installation Troubleshooting Chart