Automatic shutdown feature, Table 3-4. fault configuration for overtemp alarm – Hamilton Sundstrand Company ACT2000 User Manual

Page 49

background image

Fault Type

Persist Time

Fault Action

Motor

10 Secs

1 Sec

Motor temp > 130° C, Fault.

. If fault exists and

Motor temp > 135° C for 10 Secs, shutdown.


Motor temp > 130° C, Fault

. If fault exists and Motor

temp > 130° C for 60 Secs, shutdown.

Electronics

10 Secs

1 Sec

Electronics temp > 110° C, Fault.


If fault exists and Electronics temp > 115° C for 10 Secs,
shutdown.


Electronics temp > 110° C, Fault.


If fault exists and Electronics temp > 100° C for 15 Secs,
shutdown.

Table 3-4. Fault Configuration For OVERTEMP Alarm

Automatic Shutdown Feature

The ACT2000 has a self-protective shutdown feature. The ACT2000 will
shutdown if:

• Any two motor winding temperatures exceed 135 °C for ten (10)

seconds

or more (130

°C for 60 seconds )

• The electronics temperature exceeds 115 °C for 10 seconds or

more (100

°C for 15 seconds )

Note: The POSITION and MOTOR CURRENT feedback signals

will both be set to 0 mA when the current to the actuator
motor is removed.

WARNING

Property Damage and Injury Hazard – If the motor windings exceed
135

° C

(130

°C ) or the electronics exceed 115° C (100

°C ), the MCE will shut down power to the motor and electronics
thereby allowing the actuator to move with load. Touching the
actuator may result in serious burn injury

CH. 3: OPERATING THE ACT2000