Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
Table A--4. Rating and External Wiring Requirements for
Powerware 9315
MBM 50---160
KVA
, 380:380
VAC,
400:400
VAC,
415:415
VAC
RATING AND EXTERNAL WIRING REQUIREMENT
UNITS
RATING 50/60 HZ
BASIC UNIT RATING AT
0.8 LAGGING PF LOAD
KVA
KW
160
128
130
104
100
80
80
64
65
52
50
40
40
32
30
24
UPS INPUT VOLTAGE
BYPASS INPUT/UPS OUTPUT VOLTAGE
VOLTS
VOLTS
380/400/415
380/400/415
A
AC INPUT TO MAINTENANCE BYPASS
(3) PHASES, (1) GROUND
AMPS
231
188
146
115
97
74
60
45
A
CONDUCTOR SIZE
NUMBER PER PHASE
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
1
(1)
B
AC INPUT TO UPS BYPASS
(3) PHASES, (1) GROUND
AMPS
231
188
146
115
97
74
60
45
B
CONDUCTOR SIZE
NUMBER PER PHASE
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
1
(1)
C
AC OUTPUT TO CRITICAL LOAD
(3) PHASES, (1) NEUTRAL, (1) GROUND
AMPS
231
188
146
115
97
74
60
45
C
CONDUCTOR SIZE
NUMBER PER PHASE
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
1
(1)
D
UPS/PTC OUTPUT TO MBM CABINET (MIS)
(3) PHASE, (1) NEUTRAL, (1) GROUND
AMPS
231
188
146
115
97
74
60
45
D
CONDUCTOR SIZE
NUMBER PER PHASE
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
1
(1)
E
CONTROL WIRING TO UPS
(2) CONDUCTORS
VOLTS
AMPS
120
1
120
1
120
1
120
1
120
1
120
1
120
1
120
1
Note:
Callout letters
A, B, C, D,
and
E
map to drawing 164201177---4 (Reverse Transfer Connection) and
164201177---7 (Parallel Connection). Read and understand the notes on drawings when planning your installation.