DESCRIPTION:

DATE:

DRAWING NO:

4 of 4

INSTALLATION NOTES

SHEET:

REVISION: C

164201177---1

041500

A---5

Powerware 9315 Maintenance Bypass Module 30---160kVA

164201177 Rev. C 041500

Table A--4. Rating and External Wiring Requirements for

Powerware 9315

MBM 50---160

KVA

, 380:380

VAC,

400:400

VAC,

415:415

VAC

RATING AND EXTERNAL WIRING REQUIREMENT

UNITS

RATING 50/60 HZ

BASIC UNIT RATING AT

0.8 LAGGING PF LOAD

KVA

KW

160

128

130

104

100

80

80

64

65

52

50

40

40

32

30

24

UPS INPUT VOLTAGE

BYPASS INPUT/UPS OUTPUT VOLTAGE

VOLTS

VOLTS

380/400/415

380/400/415

A

AC INPUT TO MAINTENANCE BYPASS

(3) PHASES, (1) GROUND

AMPS

231

188

146

115

97

74

60

45

A

CONDUCTOR SIZE

NUMBER PER PHASE

AWG/MCM

(each)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

1

(1)

1

(1)

1

(1)

B

AC INPUT TO UPS BYPASS

(3) PHASES, (1) GROUND

AMPS

231

188

146

115

97

74

60

45

B

CONDUCTOR SIZE

NUMBER PER PHASE

AWG/MCM

(each)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

1

(1)

1

(1)

1

(1)

C

AC OUTPUT TO CRITICAL LOAD

(3) PHASES, (1) NEUTRAL, (1) GROUND

AMPS

231

188

146

115

97

74

60

45

C

CONDUCTOR SIZE

NUMBER PER PHASE

AWG/MCM

(each)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

1

(1)

1

(1)

1

(1)

D

UPS/PTC OUTPUT TO MBM CABINET (MIS)

(3) PHASE, (1) NEUTRAL, (1) GROUND

AMPS

231

188

146

115

97

74

60

45

D

CONDUCTOR SIZE

NUMBER PER PHASE

AWG/MCM

(each)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

1

(1)

1

(1)

1

(1)

E

CONTROL WIRING TO UPS

(2) CONDUCTORS

VOLTS

AMPS

120

1

120

1

120

1

120

1

120

1

120

1

120

1

120

1

Note:

Callout letters

A, B, C, D,

and

E

map to drawing 164201177---4 (Reverse Transfer Connection) and

164201177---7 (Parallel Connection). Read and understand the notes on drawings when planning your installation.