DESCRIPTION:

DATE:

DRAWING NO:

1 of 4

INSTALLATION NOTES

SHEET:

REVISION: C

164201177---1

041500

A---2

Powerware 9315 Maintenance Bypass Module 30-160kVA

164201177 Rev. C 041500

Table A--1. Ratings & External Wiring Requirements for

Powerware 9315

MBM 30---160

kVA

, 480:208

VAC

/600:208

VAC

Rating and External Wiring Requirement

Units

Rating 60 Hz

Basic unit rating at

0.8 lagging PF load

KVA

KW

160

128

130

104

100

80

80

64

UPS Input Voltage/Bypass Input

UPS Output Voltage

VOLTS

VOLTS

480

208

600

208

480

208

600

208

408

208

600

208

480

208

600

208

A

AC Input to Maintenance Bypass

(3) Phases, (1) Ground

AMPS

192

153

156

125

120

96

96

77

A

Conductor Size

Number per Phase

AWG/MCM

(each)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

1

(1)

1

(1)

B

AC Input to UPS Bypass

(3) Phases, (1) Ground

AMPS

192

153

156

125

120

96

96

77

B

Conductor Size

Number per Phase

AWG/MCM

(each)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

1

(1)

1

(1)

C

AC Output to Critical Load

(3) Phases, (1) Neutral, (1) Ground

AMPS

444

444

361

361

278

278

222

222

C

Conductor Size

Number per Phase

AWG/MCM

(each)

400

(2)

400

(2)

400

(2)

400

(2)

400

(2)

400

(2)

300

(1)

300

(1)

D

UPS/PTC Output to MBM Cabinet (MIS)

(3) Phases, (1) Neutral, (1) Ground

AMPS

444

444

361

361

278

278

222

222

D

Conductor Size

Number per Phase

AWG/MCM

(each)

400

(2)

400

(2)

400

(2)

400

(2)

400

(2)

400

(2)

300

(1)

300

(1)

E

Control Wiring to UPS

(2) Conductors

VOLTS

AMPS

120

1

120

1

120

1

120

1

120

1

120

1

120

1

120

1

Basic unit rating at

0.8 lagging PF load

KVA

KW

65

52

50

40

40

32

30

24

UPS Input Voltage/Bypass Input

UPS Output Voltage

VOLTS

VOLTS

480

208

600

208

480

208

600

208

480

208

600

208

480

208

600

208

A

AC Input to Maintenance Bypass

(3) Phases, (1) Ground

AMPS

78

63

60

48

48

38

36

29

A

Conductor Size

Number per Phase

AWG/MCM

(each)

1

(1)

1

(1)

1

(1)

1

(1)

1

(1)

1

(1)

1

(1)

1

(1)

B

AC Input to UPS Bypass

(3) Phases, (1) Ground

AMPS

78

63

60

48

48

38

36

29

B

Conductor Size

Number per Phase

AWG/MCM

(each)

1

(1)

1

(1)

1

(1)

1

(1)

1

(1)

1

(1)

1

(1)

1

(1)

C

AC Output to Critical Load

(3) Phases, (1) Neutral, (1) Ground

AMPS

180

180

139

139

111

111

83

83

C

Conductor Size

Number per Phase

AWG/MCM

(each)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

D

UPS/PTC Output to MBM Cabinet (MIS)

(3) Phases, (1) Neutral, (1) Ground

AMPS

180

180

139

139

111

111

83

83

D

Conductor Size

Number per Phase

AWG/MCM

(each)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

300

(1)

E

Control Wiring to UPS

(2) Conductors

VOLTS

AMPS

120

1

120

1

120

1

120

1

120

1

120

1

120

1

120

1

Note:

Callout letters

A, B, C, D,

and

E

map to drawing 164201177---5 (Reverse Transfer Connection) and

164201177---8 (Parallel Connection). Read and understand the notes on drawings when planning your installation.