beautypg.com

1 ups control logic, Sola 4000 - pcb description – Powerware Uninterruptible Power Supply SOLA 4000 User Manual

Page 95

background image

SOLA 4000 - PCB Description

JUE 401268

95

CPHC16 - R Front View

FIG. 1.2 illustrates the display, switches and connectors of the
CPHC16 - R PCB which are accessible from the front.

- 7 segment display for diagnostics (see table below)

- Reset max. Vdc pushbutton: press when the character "4" is

displayed or the central segment is blinking.

- Reset Boost Charge Alarm

- Reset after EPO (V2.1)

- RS232 connector (male)

- RS485 connector (female)

1 UPS Control Logic

DIAGNOSTICS

RESET MAX. Vdc

RS 232

RS 485

Priority

Indication

Diagnostics

1

8

E²PROM failure

2

2

Fuse blown

3

C

Mains not OK

4

P

Wrong phase rotation

5

3

Overtemperature

6

4

Overvoltage

7

Ø

Pulse release missing

8

9

Rectifier failure

9

6

Fan failure

10

L

Overload

--

Boost charge

"--"

(when blinking)

Has left the boost

charge due to a given

time limit but the

battery was not

completely charged.
Reset with "RESET

max. Vdc" above.