beautypg.com

1 installation, Sola 4000 - installation and initial start-up – Powerware Uninterruptible Power Supply SOLA 4000 User Manual

Page 24

background image

SOLA 4000 - Installation and Initial Start-Up

JUE 401265

24

Version 2 SOLA 4000 with Separate Inputs

for Rectifier and Bypass

Input Cables

Type

SOLA

4000

Rect.

cables

[mm²]

Bypass

cables

[mm²]

earth

cable

[mm²]

10

3x10

4x10

16

15

3x10

4x10

16

20

3x16

4x16

16

30

3x25

4x25

25

40

3x25

4x25

25

60

3x35

4x35

25

80

3x50

4x50

50

100

3x70

4x70

50

120

3x120

4x120

70

TAB. 1.2.3 UPS input cables, version 2

Input Fuses

Type

SOLA

4000

Rect.

Fuses

[A]

Bypass Fuses

[A]

10

25

25

15

35

35

20

50

50

30

63

63

40

100

100

60

100

125

80

125

160

100

160

200

120

200

250

TAB. 1.2.4 UPS input fuses, version 2

Output / Battery Cables

Type

SOLA

4000

Battery

cables

[mm²]

Output cables

[mm²]

Max. inv. input

current

(Vdc=320V)

10

2x16

4x10

25

15

2x16

4x10

40

20

2x25

4x16

50

30

2x25

4x35

75

40

2x35

4x25

100

60

2x50

4x35

150

80

2x70

4x50

200

100

2x95

4x70

250

120

2x120

4 x120

300

TAB. 1.2.5 UPS output cables and fuses, version 2

1 Installation