beautypg.com

1 installation, Sola 4000 - installation and initial start-up – Powerware Uninterruptible Power Supply SOLA 4000 User Manual

Page 22

background image

SOLA 4000 - Installation and Initial Start-Up

JUE 401265

22

Version 1 SOLA 4000 with Common Input for

Rectifier and Bypass

Input Cables / Fuses

Type

SOLA

4000

Input

cables

[mm²]

Input

fuses

[A]

earth

cable

[mm²]

10

4x10

25

16

15

4x10

35

16

20

4x16

50

16

30

4x25

63

25

40

4x35

100

25

60

4x35

125

25

80

4x70

160

50

100

4x70

200

50

120

4x120

250

70

TAB.1.2.1 UPS input cables
and fuses, version 1

Output / Battery Cables and Max. Cur-

rent Ratings for Battery Overcurr. pro-

tection

Type

SOLA

4000

Battery

cables

[mm²]

Output cables

[mm²]

Max. inv. input

current

(Vdc=320V)

10

2x16

4x10

25

15

2x16

4x10

40

20

2x25

4x16

50

30

2x25

4x35

75

40

2x35

4x25

100

60

2x50

4x35

150

80

2x70

4x50

200

100

2x95

4x70

250

120

2x120

4 x120

300

TAB.1.2.2 UPS output cables and fuses, version 1