SOLA 4000 - Installation and Initial Start-Up
JUE 401265
22
Version 1 SOLA 4000 with Common Input for
Rectifier and Bypass
Input Cables / Fuses
Type
SOLA
4000
Input
cables
[mm²]
Input
fuses
[A]
earth
cable
[mm²]
10
4x10
25
16
15
4x10
35
16
20
4x16
50
16
30
4x25
63
25
40
4x35
100
25
60
4x35
125
25
80
4x70
160
50
100
4x70
200
50
120
4x120
250
70
TAB.1.2.1 UPS input cables
and fuses, version 1
Output / Battery Cables and Max. Cur-
rent Ratings for Battery Overcurr. pro-
tection
Type
SOLA
4000
Battery
cables
[mm²]
Output cables
[mm²]
Max. inv. input
current
(Vdc=320V)
10
2x16
4x10
25
15
2x16
4x10
40
20
2x25
4x16
50
30
2x25
4x35
75
40
2x35
4x25
100
60
2x50
4x35
150
80
2x70
4x50
200
100
2x95
4x70
250
120
2x120
4 x120
300
TAB.1.2.2 UPS output cables and fuses, version 1