SOLA 4000 - Operating Panel
5 Remote Panel
Communication timing
When an alarm condition occurs, the Remote Panel calls the first
programmed number.
If the line is busy and only one number is to be called, the Remote
Panel waits for 5 minutes and, if the alarm condition is still present,
it tries to call the number again. This procedure will be repeated
until the connection has been established or the alarm condition
ends.
If the line is busy and two numbers are to be called, the second
number will be called. If this line is also busy the first number will
be tried again and so on.
After a successful connection the Remote Panel will normally hold
the line for five minutes. Any additional alarm messages that are
activated during that time will be displayed automatically at the
computer display and one minute will be added to the remaining
connection time. The maximum connection time is, however,
limited to ten minutes.
If during the connection all alarms are deactivated, the Remote
Panel sends the following messages:
UPSx
followed by:
UPS OK
and the remaining connection time is set to one minute.
5.4 DIP-switch settings
DIP Switch DIP1
switch 1
Not used
ON
OFF
switch 2
Local buzzer
ON
active
OFF
not active
switch 3
Automatic call
ON
active
OFF
not active
switch 4
Phone numbers
ON
two phone numbers
OFF
one phone number
switch 5
Not used
ON
-
OFF
-
sw. 6
sw. 7
sw. 8
UPS number for
identification
ON
ON
ON
1
OFF
ON
ON
2
ON
OFF
ON
3
OFF
OFF
ON
4
ON
ON
OFF
5
OFF
ON
OFF
6
ON
OFF
OFF
7
OFF
OFF
OFF
8
FIG. 5.1 - Setting of DIP1