SOLA 4000 - Operating Panel

5 Remote Panel

Communication timing

When an alarm condition occurs, the Remote Panel calls the first
programmed number.

If the line is busy and only one number is to be called, the Remote
Panel waits for 5 minutes and, if the alarm condition is still present,
it tries to call the number again. This procedure will be repeated
until the connection has been established or the alarm condition
ends.

If the line is busy and two numbers are to be called, the second
number will be called. If this line is also busy the first number will
be tried again and so on.

After a successful connection the Remote Panel will normally hold
the line for five minutes. Any additional alarm messages that are
activated during that time will be displayed automatically at the
computer display and one minute will be added to the remaining
connection time. The maximum connection time is, however,
limited to ten minutes.

If during the connection all alarms are deactivated, the Remote
Panel sends the following messages:

UPSx

followed by:

UPS OK

and the remaining connection time is set to one minute.

5.4 DIP-switch settings

DIP Switch DIP1

switch 1

Not used

ON

OFF

switch 2

Local buzzer

ON

active

OFF

not active

switch 3

Automatic call

ON

active

OFF

not active

switch 4

Phone numbers

ON

two phone numbers

OFF

one phone number

switch 5

Not used

ON

-

OFF

-

sw. 6

sw. 7

sw. 8

UPS number for

identification

ON

ON

ON

1

OFF

ON

ON

2

ON

OFF

ON

3

OFF

OFF

ON

4

ON

ON

OFF

5

OFF

ON

OFF

6

ON

OFF

OFF

7

OFF

OFF

OFF

8

FIG. 5.1 - Setting of DIP1