SOLA 4000 - Installation and Initial Start-Up

JUE 401265

42

1.12 Battery Installation

Battery Installation must be in accordance with local safety
standards.

General

The batteries are charged. The installation should only be made by
appropriately qualified personnel. The screw connections between
the batteries should be tightened with a torque wrench (max. 7
Nm).

1.12.1 Installation of Internal batteries
SOLA 4000 (10-30kVA)

Internal Battery (24Ah) Installation

• Place five battery blocks on the trays of the first level.

• Place nine battery blocks on the trays of the second, third and
fourth level.

• Interconnect the blocks in series (see FIG.1.12.1)

Warning: after assembly there is a voltage of 67,5 V on the first
level, and 121,5 V on the second, third and fourth levels.

1° LEVEL

2° LEVEL

3° LEVEL

4° LEVEL