SOLA 4000 - Operating Panel

3.2 SNMP MODE

With DIP7 of SW2 in the ON position, the UPS can be monitored
and controlled from a remote location by a PC through a SNMP
protocol converter. In this mode, software packages such as
SMARTMON

from Systems Enhancement Corporation may be

directly applied using a P.C.

The software runs on PCs with the following Operating systems:

M

ICROSOFT

WINDOWS

M

ICROSOFT

WINDOWS

FOR

W

ORKGROUPS

M

ICROSOFT

WINDOWS

95

M

ICROSOFT

WINDOWS

NT

IBM OS/2

The software allows:

- UPS monitoring

- Event logging

- Broadcasting

- Paging

- E - Mail (only for Windows 95)

The use of a modem for remote monitoring is also possible.

The UPS can be connected to a LAN and monitored through an
SNMP protocol.

An external Hardware interface is required to perform the protocol
conversion from SEC protocol to SNMP protocol.

3.3 Service Mode

This mode is intended as a test mode and is used during testing /
maintenance of all units. It is activated by setting DIP 7 of SW2 in
the OFF position.

PC Requirements

• A program is available for testing / service purposes.

• The communication parameters must be set as follows:

BAUD

=

1200

PARITY

=

OFF

BITs

=

8

STOP BITs

=

1

3 Communication with a PC