SOLA 4000 - Operating Panel

3.4 Alarms

With a connected PC, the following alarms are realised (SNMP and
service modes):

Rectifier Failure

The Rectifier mains is in order but a failure is present within the
rectifier.

Inverter Failure

The inverter is ON but the inverter voltage or inverter conditions
are not in order.

Battery Switch OFF

The battery switch is OFF

Retransfer blocked

The inverter has attempted unsuccesfully to take over the load at
least 5 times within 3 minutes.

To reset, press the "RESET" pushbutton a second time after
muting the alarm.

Overtemperature

The inverter/rectifier components are operating at an excessive
temperature. This can be due to extreme environmental conditions
or a failure within the inverter or rectifier sections.

If the bypass is available the UPS transfers immediately to the
bypass supply (in the case of a hot-standby system, the second
unit takes over the load, in the case of a parallel system the re-
maining inverters take over the load). If the bypass or another
inverter is not available then the UPS will continue to supply the
load for a further 10 minutes before shutting down.

Mains Failure

The mains is not present or not within the specified voltage and
frequency tolerances.

Inverter not Feeding

The inverter is not feeding the load and the bypass static switch,
SSI is OFF.

Battery Discharging

The mains or rectifier has failed and the batteries are
discharging.This alarm is activated at a battery voltage of approx.
360Vdc.

Low Battery

The remaining battery capacity during discharge has been calcu-
lated to be less than 20% of the nominal capacity.

Battery Test Failed

The routine battery test has detected a decrease in capacity of the
battery. The battery must be checked.

Paralleling Fault

The inverter has failed to regulate correctly in parallel operation
with another inverter (parallel systems only).

Bypass not Available

The bypass mains supply is OK but the bypass is not available to
take the load if the inverter fails (the inverter is not synchronised or
is blocked externally).