beautypg.com

2 rectifier data, Sola 4000 - technical data – Powerware Uninterruptible Power Supply SOLA 4000 User Manual

Page 106

background image

SOLA 4000 - Technical Data

JUE 401269

106

IG. 2.1 - Rectifier Data

2 Rectifier Data

Technical Data / Rectifier Data

Type SOLA 4000

10

15

20

30

40

60

80

100

120

Input voltage
Tolerance
with reduced output (DC) voltage

refer to system data
refer to system data
-20 %

Input frequency
Tolerance

refer to system data
± 10 %

Rated input power with charged battery
- [kVA]

10,8

16

21,3

32

42,7

64,1

84,8

106

127,4

Rated input current with charged battery
(380 V) [A]

16,4

24,6

32,7

49,2

65

97,5

128,5

160,7

193

Maximum input power
- [kVA]

13,5

20

26,9

39,8

53,5

80

105

132

158

Maximum input current, input voltage = 380 V
- [A]

20,5

30,8

40,8

61,2

81,5

122

160,5

201

241

Input power factor
( nom. load, input voltage = 380V)

~ 0,83 lag.

Output control characteristics

I/U characteristic, boost charge possible

Rated output voltage
- Lead-Acid batteries
- Ni-Cd batteries

432 V/DC
436 V/DC (depending on number of cells)

Soft start

~ 10 sec.

Floating voltage regulation with load between 0
and 100%

1 %

Output voltage ripple with battery disconnected

RMS 1 %

Max. batt. recharging current with nom. load
- [A]

5

7,5

10

15

20

30

40

50

60

Battery charging current limitation

Complies with battery manufacturer's recommendations,
standard setting approximately 10% of rated battery capacity