TROUBLESHOOTING

E-14

POWER WAVE® AC/DC 1000

Observe all Safety Guidelines detailed throughout this manual

If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely, contact your
Local Lincoln Authorized Field Service Facility for technical troubleshooting assistance before you proceed.

CAUTION

WIRE DRIVE MODULE

Error Code #

81 Motor Overload

82 Motor Overcurrent

83 Shutdown #1

84 Shutdown #2

Indication

Long term average motor current limit has been exceeded. Typically
indicates mechanical overload of system. If problem continues consider
higher gear ratio.

Absolute maximum motor current level has been exceeded. This is a
short term average to protect drive circuitry.

The normally closed circuit of Shutdown #1 has been interrupted.
Check the connection between pins 9 and 10 on the External I/O con-
nector (S7).

The normally closed circuit of Shutdown #2 has been interrupted.
Check the connection between pins 9 and 11 on the External I/O con-
nector (S7).

COMMUNICATION MODULE

Error Code #

118 DeviceNet connection error

119 DeviceNet de-allocation error

133 Write ArcLink action failure

145 Duplicate MAC ID error

146 DeviceNet Bus off

147 DeviceNet polled I/O error

149 DeviceNet I/O data error

169 Ethernet Connection Time out
171 Ethernet Socket Time out
172 Ethernet Watch Dog Time out

194 Ethernet Send Problem
195 Ethernet Problem
197 Ethernet Problem

198 Ethernet Client Time out

216 Ethernet Problem

224 Ethernet Problem

226 Ethernet Problem

Indication

Lost Connection with DeviceNet Master

The DeviceNet Master de-allocated the connection

May be caused by activating Cold Inch while welding through
DeviceNet

Check MAC ID assignments on DeviceNet Setup Dip switch Bank (S2)

Check condition of on board DeviceNet Status indicators

Problem changing attribute over polled I/O

Received DeviceNet I/O data with wrong number of bytes

Loss of communication with PC Application.

Communication problem between Master and Slave machines.

Master lost communications with Slave Machine.

Communication problem between Master and Slave machines.

Master had problem connecting to a Slave machine.

Communication problem between Master and Slave machines.