A
Building Safety. Building Security.
Specifi cations
Mains voltage
230VAC +10/-15%, 50Hz
Connection power
60VA
Output voltage
typ. 28VDC
Output peak current
max. 1.8A
Connection of external devices
typ. 0.8A, site-specifi c
Own current consumption at 24V
BC216-2: typ. 125mA (without optional componentries)
BC216-3: typ. 90mA (without optional componentries)
Ambient temperature
-5°C to +50°C
Dimensions W × H × D
420 Ч 520 Ч 120 (mm)
Colour
gray-white, RAL 9002
Weight without accumulator
approx. 6kg
Approvals (EN 54-2, EN 54-4)
VdS G201017
FT 14/147/3/99 (Austria),
Sectional control panel with display and operating unit
Order name
BCnet Sectional control panel/Op. BC216-2
Sectional control panel without display and operating unit
Order name
BCnet sectional control panel/n. op. BCnet216–3
Permanent Connection
A variety of peripheral devices can be connected to the
fi re detection control panel BCnet216:
• Fire brigade key safe
• Fire brigade control unit
• Acoustic and optical signaling devices
• External protocol printer
• Remote display and operating panels
• Remote indication unit
• Actuations
• Electronic monitoring system
• Transmitting device for the actuation of pagers via
ESPA protocol
• Modules for remote parameterisation and remote
maintenance via computer newtork, modem or GSM
connection
• Transmitter module for the transmission of messages
via SMS or e-mail
– and much more.
If required, the BCnet216 can be easily expanded to
an extinguishing control panel LCnet216 according to
EN 12094-1. The panel can control up to 127 fl ooding
zones in a maximum of 127 extinguishing systems.
The function of the extinguishing control panel is fully in-
tegrated into the fi re detection control panel BCnet216,
a combined operation is therefore possible.
The LCnet216 is certifi ed to EN 54-2, EN 54-4,
EN 12094-1 and VdS as a pure extinguishing control
panel and as a combined fi re detection and extinguis-
hing control panel.
Optionally, the LCnet216 can be implemented with full
hardware redundancy.
Extinguishing Control System