A
Building Safety. Building Security.
Description
The Thermal Max Detector 4351E recognises a maxi-
mum temperature of 78°C as sign of fi re. It complies
with Class BS and can be used up to a room height
of 6m.
Addressable conventional technology is used for alarm
transmission to the fi re detection control panel. The
detector addressing can be achieved in 2 ways:
• A detector with an Address Module NG58-1 can be
individually identifi ed by the suitable control panel.
• An address, which has been stored in the detector
by means of the Remote Programming and Test Unit,
is displayed on the Zonal Display Unit S300ZDU.
A test activation of the detector can be carried out
using the Remote Test Unit ECO1000RTU. In addition
to the test activation of the detector, the Remote Pro-
gramming and Test Unit S300RPTU can also be used
to set and display the following detector parameters:
• the detector address, and
• the date of the previous maintenance.
The detector can be attached to various detector ba-
ses and it can be protected against theft.
• Addressable conventional technology
• Alarm temperature 78°C
• Addressing by means of address
module or detector parameterisation
• Remote readout of detector condition
• Function testable with Remote Test
Unit ECO1000RTU
Specifi cations
Operating voltage
Supply through the detector line voltage
Current consumption
typ. 85µA (quiescent)
Alarm temperature
78°C
Ambient temperature
-30°C to +70°C (continuous operation)
Relative humidity
5 – 95% (no condensation)
Dimensions ш Ч H
102 × 43 (mm)
Colour
cream
Weight
75g
Approval
VdS G202016
Order number
242041
Order name
Thermal Max Detector/Conv./300/SS 4351E