Building Safety. Building Security.

• Addressable conventional technology
• Maximum temperature 57°C
• Individual detector addressing by

means of optional address module

• Optional connection of remote

indicator

• Sealed electronics

Description

The Thermal ROR Detector GD-55000-122 reacts to

temperature changes within defi ned periods of time,

up to a maximum temperature of 57°C. The intelligent

evaluation of these data allows the early detection of

spreading fi res. The detector complies with Class A1R

and can be used up to a room height of 7.5m.

Addressable conventional technology is used for alarm

transmission to the fi re detection control panel. By

means of the optional Address Module NG60-1, each

detector can be addressed individually. With that, the

activated detector can also be safely identifi ed directly

on the control panel.

The detector can be attached to various bases and it

can be protected against theft.

Specifi cations

Operating voltage

Supply through the detector line voltage

Current consumption

typ. 45µA (quiescent)

Alarm temperature

57°C (maximum-heat component)

Operating temperature

max. +50°C

Ambient temperature

-20°C to +90°C (no condensation or icing)

Relative humidity

0 – 95% (no condensation)

Dimensions ш Ч H

100 × 42 (mm)

Colour

white

Weight

80g

Approval

VdS G200059

Order number

242024

Order name

Thermal ROR Detector/Conv./65/Apo GD-55000-122